SFA ZPS 1.3 Operation And Assembly Instructions Download Page 9

9

1st line on display

2nd line on display

(set value)

Signification

delay time

0 to 180 sec

The turn-on delay of the pump only functions 

after a restart of the control system (e.g. 

after a power failure). With “normal” switch 

operation via the levels N1 and N2, this 

setting is not relevant.
This function may be used to avoid the 

simultaneous switch-on of several pumping 

station after mains failure.

overrun

0-180 sec.

After having reached the turn-off level, the 

pump is still running for the adjusted amount 

of time.

max. current.
P1

0,0 to 14,0 A

If the adjusted value is reached, the 

monitoring system of the pump motor current 

effectuates the shutdown of the pump, 

accompanied by a notice of malfunction.
The malfunction has to be acknowledged 
manually by pressing the key 

.

Attention :

 If the nominal current is 

adjusted to 0 A no monitoring of the motor’s 

charging rate occurs !

24 hours start

is activated
is deactivated

The pump P1 is briefly started if no request 

occurs by the switch-on level within 24 

hours.
If the ATEX mode is enabled, the 24h 

starting is only taking place if the turn-off 

level is exceeded.

acoustic alarm

is activated
is deactivated

The internal acoustic transmitter is switched 

on or off. This setting has no influence on 

the potential-free alarm signal.

interval alarm

is activated
is deactivated

The alarm relay for the non-floating alarm 

contact is synchronized or produces a 

permanent signal.

Therm. fault

Thermostatic switch
P1 TH1 control loop
     TH2 control loop

is activated

The evaluation of the thermal contacts TH1 

(control loop) can be deactivated. If this 

contact is open, the pump is shut down 

and an error is signalled. After the contact 

TH1 (control loop) has cooled down and 

been closed again, the pump restarts 

automatically.
After cooling down, the activation of the 

pump in case of malfunction TH2 can 

only be effected by acknowledging the 
malfunction by pressing the key 

This contact can not be deactivated by 

means of the software. If the pump is not 

equipped with thermal contacts, a bridge 

has to be inserted as a substitution for TH2.

Summary of Contents for ZPS 1.3

Page 1: ...Electronic pump control Operation and assembly instructions CONTROL BOX ZPS 1 3 9001 3 11 19...

Page 2: ...English 3 Deutsch 17 Fran ais 32 Italiano 47 Nederlands 62 Espa ol 76 Portugu s 91...

Page 3: ...l characteristics pg 5 2 3 Technical data pg 5 3 OPERATION OF THE CONTROL SYSTEM pg 6 3 1 Operator control panel and operational elements pg 6 3 1 1 Key pg 6 3 1 2 Indications on the display pg 7 3 1...

Page 4: ...ce of at least 3 mm The connection must be used exclusively to provide the power to the product If the power cord is damaged to prevent possible danger it must be replaced by the manufacturer customer...

Page 5: ...istics Clear LCD display Hand Stop Auto Function 1 acknowledgement button 2 parameter select buttons Menu which can be switched through Internal acoustic alarm Programmable operation and collective fa...

Page 6: ...y pressing this key the preferred pump is switched on without delay No other function of the program is enabled The green LED of one pump flashes ATTENTION If the ATEX mode is enabled the pump can onl...

Page 7: ...re displayed alternately In case of failure the actual failure status is displayed see point 3 1 6 The red LEDs of the pump will be seen red flashing light Parameter setting In the upper line the desi...

Page 8: ...sensor Flooding alarm level Additionally this level is constantly evaluated on the input for the floating switch HW independent from the selected level transmitter Thereby if necessary 2 different HV...

Page 9: ...efly started if no request occurs by the switch on level within 24 hours If the ATEX mode is enabled the 24h starting is only taking place if the turn off level is exceeded acoustic alarm is activated...

Page 10: ...via external sensor intern converter matching calibration By pressing the key sequence the zero point of the internal converter is adjusted The adjustment has to be carried out while the pilot tube i...

Page 11: ...maintenance within days XXXX in days Shows the number of days until the next maintenance The information is saved at intervals of 4 hours The initial value can be preset between 365 and 0 days 3 1 6...

Page 12: ...anually Yes Pump TH1 TH2 Phase error A phase of the power supply has failed Yes Dreh Fault ATEX The ATEX mode is activated and the level is below the switch off point of the selected pump Yes Atex Run...

Page 13: ...rding to the connection diagram shown below Connection of a 3 phase Motor Connection of a single phase Motor with internal capacitor Mains connection Pump1 Protective conductors Mains connection Pump1...

Page 14: ...t board The active sensor can be selected in the menu level control and therm malfunction If the thermostatic switch TH2 is not necessary a bridge has to be inserted on this contact point The thermost...

Page 15: ...verter adjustment serves for the accurate adjustment of the zero point In order to equalise possible air leaks inside the pneumatic level measuring device the pilot tube has to be fully emerged from t...

Page 16: ...idge thermal contacts TH2 5 Disable thermic error for the pump If the respective level sensors are connected all program functions can be checked without having to connect the pump 4 DISPOSAL Only for...