![SEW DFD11B Manual Download Page 58](http://html1.mh-extra.com/html/sew/dfd11b/dfd11b_manual_1250019058.webp)
58
Manual – DFD11B DeviceNet Fieldbus Interface
6
The Common Industrial Protocol (CIP)
DeviceNet Characteristics
DeviceNet object
• The DeviceNet object provides information on the DeviceNet communication inter-
face.
• Class code: 03
hex
Class
Instance 1
Supported ser-
vices
Attribute
Acc.
Name
Data type
Default
value [hex]
Description
1
Get
Revision
UINT
0002
Revision 2
Attribute
Acc.
Name
Description
1
Get
MAC-ID
According to DIP-switches (0 ... 63)
2
Get
Baud rate
According to DIP-switches (0 ... 2)
3
Get
BOI
4
Get/Set Bus-off Counter
Error counter of the physical CAN-Interface (0 ...
255)
5
Get
Allocation information
6
Get
MAC-ID switch changed
Information as to whether DIP switch settings vary
from MAC-ID
7
Get
Baud rate switch changed
Information as to whether DIP switch settings vary
from baud rate
8
Get
MAC-ID switch value
Actual DIP switch settings for MAC-ID
9
Get
Baud rate switch value
Actual DIP switch settings for baud rate
Service Code [hex]
Service Name
Class
Instance
0E
Get_Attribute_Single
X
X
10
Set_Attribute_Single
-
X
0
0
I