![SEW-Eurodrive Movidrive MDX60B Compact Operating Instructions Download Page 39](http://html1.mh-extra.com/html/sew-eurodrive/movidrive-mdx60b/movidrive-mdx60b_compact-operating-instructions_1250160039.webp)
6
Service
Fault messages and list of faults
Compact Operating Instructions – MOVIDRIVE
®
MDX60B/61B
39
Fault
Subfault
Code Designation Response
(P)
Code
Designation
Possible cause
Measure
108
DCS fault
Display fault 44
Digital output range check
is faulty.
Faulty configuration data of di-
gital outputs.
• Undo the changes in the
disconnection matrix of the
digital outputs or enter new
values.
• Reload the configuration
data. Next switch the
DCS..B option off and on
again.
• If the fault occurs again,
contact SEW‑EURODRIVE
Service for the proper
MOVISAFE
®
software ver-
sion.
45
Digital output range check
is faulty.
Faulty configuration data of di-
gital outputs.
• Undo the changes in the
disconnection matrix of the
digital outputs or enter new
values.
• Reload the configuration
data. Next switch the
DCS..B option off and on
again.
• If the fault occurs again,
contact SEW‑EURODRIVE
Service for the proper
MOVISAFE
®
software ver-
sion.
46
Encoder type range check
is faulty.
Incorrectly configured encoder
type.
• Undo the changes in the
encoder configuration or
enter new values.
• Reload the configuration
data. Next switch the
DCS..B option off and on
again.
• If the fault occurs again,
contact SEW‑EURODRIVE
Service for the proper
MOVISAFE
®
software ver-
sion.
24770531/EN – 11/2017
Summary of Contents for Movidrive MDX60B
Page 2: ...SEW EURODRIVE Driving the world...
Page 60: ......
Page 61: ......
Page 62: ......