![SEW-Eurodrive Movidrive MDX60B Compact Operating Instructions Download Page 35](http://html1.mh-extra.com/html/sew-eurodrive/movidrive-mdx60b/movidrive-mdx60b_compact-operating-instructions_1250160035.webp)
6
Service
Fault messages and list of faults
Compact Operating Instructions – MOVIDRIVE
®
MDX60B/61B
35
Fault
Subfault
Code Designation Response
(P)
Code
Designation
Possible cause
Measure
108
DCS fault
Display fault 32
The range check of the ac-
cess data is faulty.
Faulty configuration data of the
device description.
• Reload the configuration
data. Next switch the
DCS..B option off and on
again.
• If the fault occurs again,
contact SEW‑EURODRIVE
Service for the proper
MOVISAFE
®
software ver-
sion.
33
EMU range check is faulty. Faulty configuration data of the
EMU function.
• Undo the changes in the
EMU configuration or enter
new values.
• Reload the configuration
data. Next switch the
DCS..B option off and on
again.
• If the fault occurs again,
contact SEW‑EURODRIVE
Service for the proper
MOVISAFE
®
software ver-
sion.
34
PSC range check is faulty. Faulty configuration data of the
PSC function.
• Undo the changes in the
PSC configuration or enter
new values.
• Reload the configuration
data. Next switch the
DCS..B option off and on
again.
• If the fault occurs again,
contact SEW‑EURODRIVE
Service for the proper
MOVISAFE
®
software ver-
sion.
24770531/EN – 11/2017