
MOVIDRIVE
®
PROFIBUS DFP11A
7
Assembly / Installation
Instructions
2
2
Assembly / Installation Instructions
2.1
Supported Drive Inverter Types
The DFP11 option pcb for connection to a PROFIBUS-FMS/DP system can be used with all drive
inverters of the MOVIDRIVE
®
family.
2.2
Fitting the Option PCB
Before you begin:
• Discharge yourself with appropriate measures (earthing band, conductive shoes, etc.) before
touching the option pcb.
• Store the option pcb in the original package and only unpack immediately before installation.
• Do not touch the option pcb more often than necessary and hold only by the edges. Do not
touch components.
Installation of the option pcb :
• Disconnect inverter from the supply. Switch off mains and, if applicable, 24 V supply.
• Take off the lower protective cover of the control unit.
• Untighten screws of the electronics shielding terminal.
• Remove black sheet metal cover.
• Insert option pcb into the guide rails of OPTION1 or OPTION2 slots.
• Press the front plate carefully to plug in option pcb. The pcb is correctly inserted when the front
is flush with the controller pcb.
• Fasten electronics shielding terminal.
• Replace the protective cover of the control unit.
• Depending on the D type connector used, it may not be possible to replace the protective cover.
This does not effect the enclosure of the unit.
• The DFP11 option pcb is now completely fitted.