MOVIDRIVE
®
PROFIBUS DFP11A
11
Assembly / Installation
Instructions
2
It is not possible to change the PROFIBUS station address via the DIP switches while the drive
inverter is running. If the station address is changed, the new station address will only be effective
after the drive inverter has been switched off (mains supply and 24 V supply ON/OFF) and then
switched on again. The station address set for the drive inverter is displayed with the fieldbus mon-
itor parameter P092 Fieldbus Address on the DBG Keypad or on the MX_SHELL.
01223AEN
Fig. 7: Displaying the current PROFIBUS station address on the DBG Keypad or MX_SHELL
2.7
Setting the Bus Parameters
The default value setting for the bus parameters depends on the protocol version used. For straight
PROFIBUS-DP mode the DIP switch must be set at DP. This will activate the default bus parame-
ters (in particular the min. TSDR) for time-optimized DP mode in accordance with DIN E 19245
Part 3 / EN 50170. For mixed mode (FMS/DP) or straight FMS mode the DIP switch must be set at
FMS.
00083AEN
Fig. 8: Setting the default bus parameters to DIN 19245
This switch only serves to select the default bus parameters. Independent of the setting of this
switch, the drive inverter at any time supports simultaneous use of the PROFIBUS protocol options
FMS and DP (Combislave functionality).
Any change to this DIP switch setting will only become effective after the drive inverter has been
switched off (mains supply and 24 V supply ON/OFF) and switched on again.
2.8
Display Elements
LED Green RUN LED Red BUS FAULT
Meaning
Flashing at approx.
3 Hz
Off
Option pcb is being initialized (only immediately after drive inverter power-up or reset)
On
Flashing at approx. 0.5 Hz Configured station address is not within the permitted range (0...126)
→
Set correct
station address and switch the unit on again.
On
On
DP mode:
a) When the drive inverter is being commissioned or run up:
The drive inverter has not been set to data exchange mode by the DP master yet .
b) The timeout period has elapsed, the drive inverter was not addressed by the DP
master.
FMS mode: There is no active FMS link between the FMS master and the drive inverter.
Mixed mode FMS/DP: A combination of the above
4
092
Fieldbus Address
FMS/DP
DP
1 2 3 4
1 2 3 4
Address
Default bus parameters for
- FMS mode or
- FMS + DP mixed mode
Condition as delivered
FMS/DP active
Default bus parameters for
straight DP-PROFIBUS mode