48
MOVIDRIVE
®
PROFIBUS DFP11A
Appendix
Appendix
Appendix A
The definition for cable type A for PROFIBUS-DP is set forth in DIN E 19245 Part 3:
Appendix B
CRL Definition
The communications relationship lists for the PROFIBUS-FMS contain various elements of defini-
tion. For a more detailed explanation please refer to DIN 19245 Part 2.
The following tables show the individual communications relationships supported by the
MOVIDRIVE
®
drive inverter. Although the drive inverter does not use any Event services, i.e. the
drive inverter cannot execute a slave initiative, communications links with slave initiative are
supported. Whereas the Physical Read and Physical Write services are supported according to the
CRL, no Physical Write access can be executed.
Table 20: CRL for master-slave, cyclic, Read
Table 21: CRL for master-slave, cyclic, Write
Parameter:
Cable type A PROFIBUS-DP
Surge impedance
135 ... 165 Ohm (3 ... 20 MHz)
Capacitance per unit length
< 30 pF/m
Loop resistance
< 110 Ohm/km
Core diameter
> 0.64 mm
Core cross-section
> 0.34 mm
2
CREF
Type
ATTR
LSAP
RSAP
RADR
SCC
RCC
SAC
RAC
ACI/CCI
2
MSZY
O
20
All
All
0
0
0
0
3000
max PDU Size:
Features supported
Supported FMS services
Send HiPrio
0
00 00 00 00 20 00
Read.indication
Send LoPrio
241
Rec. HiPrio
0
Rec. LoPrio
241
CREF
Type
ATTR
LSAP
RSAP
RADR
SCC
RCC
SAC
RAC
ACI/CCI
3
MSZY
O
21
All
All
0
0
0
0
3000
max PDU Size:
Features supported
Supported FMS services
Send HiPrio
0
00 00 00 00 10 00
Write.indication
Send LoPrio
241
Rec. HiPrio
0
Rec. LoPrio
241