Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
89
10
PROFINET configuration with topology detection
PROFINET IO Configuration
10.3.2 Configuring the PROFINET topology
The configuration procedure for a PROFINET topology will be described using the ex-
ample of SIMATIC STEP 7. There are various approaches for configuration in
SIMATIC STEP 7. This example will focus on one approach.
1. In STEP 7 HW Config, import the PROFINET devices from the hardware catalog into
the PROFINET network as usual.
Make sure that the PROFINET IO controller supports topology detection. The con-
troller manufacturer will provide according information.
The hardware catalog contains several entries for each SEW interface marked as dif-
ferent versions. An entry marked with 'ALT' does not support the PROFINET IO to-
pology detection.
2. Right-click on the 'PROFINET IO system' and select 'PROFINET IO topology' from
the context menu.
The 'Topology editor' window is displayed.
12099AXX