![SEW-Eurodrive DHR41B Manual Download Page 41](http://html.mh-extra.com/html/sew-eurodrive/dhr41b/dhr41b_manual_1250086041.webp)
Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
41
6
CIP object directory
The Ethernet Industrial Protocol (EtherNet/IP)
Instance 161 -
SEW PO data
range
This instance is used to access the DHR41B process output data. MOVIDRIVE
®
can be
controlled by only one scanner. Therefore, only one connection can be established with
this instance.
Instance 121 -
"Heartbeat"
This instance is accessed when the scanner wants to establish an input only connection.
No process output data is sent with this type of connection. It is used only to read pro-
cess input data.
Instance 171 -
SEW PI data range
This instance is used to access the DHR41B process input data. Several multicast con-
nections or a point-to-point connection can be established to this instance.
Supported
services
Attri-
bute
Acces
s
Name
Data type
Default value
[hex]
Description
3
Get
Data
Array of
BYTE
-
OUTPUT assembly
Attri-
bute
Acces
s
Name
Data type
Default value
[hex]
Description
3
Get
Data
Array of
BYTE
-
OUTPUT assembly
Data size = 0
Attri-
bute
Acces
s
Name
Data type
Default value
[hex]
Description
3
Get
Data
Array of
BYTE
-
INPUT assembly
TIP
The names "INPUT assembly" and "OUTPUT assembly" refer to the processes as
seen from the networkÕs point of view. "INPUT assembly" produces data on the net-
work, an "OUTPUT assembly" consumes data from the network.
Service code [hex]
Service Name
Class
Instance 161 Instance 121 Instance 171
0E
Get_Attribute_Single
X
X
-
X
0
0
I
Summary of Contents for DHR41B