Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
21
4
Setting the IP address parameters
Assembly and Installation Notes for Ethernet
Deactivating/acti-
vating DHCP
The type of IP address allocation is determined by the setting of the attribute
Configura-
tion Control
of the EtherNet/IP TCP / IP interface object. The value is displayed or mod-
ified in the parameter
P785 DHCP / Startup Configuration
.
• Setting "Saved IP parameters"
The saved IP address parameters are used.
• Setting "DHCP"
The IP address parameters are requested by a DHCP server.
If you use the DHCP server from Rockwell Automation, you can activate or deacti-
vate the DHCP via a button. In this case, an EtherNet/IP telegram is sent to the
TCP/IP interface object of the station that is being addressed.
Resetting the IP
address
parameters
If you do not know the IP address parameters and there is no other interface for reading
the IP address, you can reset the IP address parameters to the default values using the
DIP switch "2
0
".
This action resets the DHR41B option to the following default values:
• IP address: 192.168.10.4
• Subnet mask: 255.255.255.0
• Default gateway: 192.168.10.4
• DHCP / Startup Configuration: Saved IP parameters (DHCP is deactivated)
Proceed as follows to reset the IP address parameters to the default values:
• Switch off the 24 V DC supply voltage and the mains voltage.
• Set the DIP switch "2
0
" on the DHR41B option to "1".
• Switch the DC 24 V supply voltage and the line voltage back on.
SEW Address
Editor
You can also use the SEW Address Editor to access the IP settings of DHR41B without
the Ethernet settings of the PC and DHR41B having to match.
The IP settings of all SEW units can be made and displayed in the local subnetwork us-
ing Address Editor in MOVITOOLS
®
MotionStudio (see section 10).
• Thus, for a running installation, you can determine the PC settings required to pro-
vide for an access with the required diagnostics and engineering tools via Ethernet.
• When starting up a unit, the IP settings for DHR41B can be assigned without chang-
ing the network connections or PC settings.
TIP
• DHCP remains deactivated when you reset the DIP switch "2
0
" (Def IP) to "0". You
can re-activate DHCP via the EtherNet/IP TCP/IP interface object (see section 'Eth-
erNet/IP CIP object directory'), via the parameter, or via the DHCP server from
Rockwell Automation.
• DHCP is activated again when the values are reset to the factory setting.