Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
115
11
Parameterization via PROFIdrive data record 47
Operating Behavior (PROFINET IO)
Query parameter response
The following table shows the coding of the READ.req user data including the
PROFINET header.
Positive PROFIdrive parameter response
The table shows the READ.res user data with the positive response data of the param-
eter setting request. The parameter value for index 8300 (firmware version) is returned
as an example.
Service:
READ.request
Description
Slot_Number
0
Random, (is not evaluated)
Index
47
Index of the data record; constant index 47
Length
240
Maximum length of response buffer in the PN controller
Service:
READ.request
Description
Slot_Number
0
Random, (is not evaluated)
Index
47
Index of the data record; constant index 47
Length
10
10 byte user data in response buffer
Byte
Field
Value
Description
0
0x01
Mirrored reference number from the parameter setting request
1
Response ID
0x01
Positive response for 'Request Parameter'
2
Axis
0x00
Reflected axis number
0 = single axis
3
No. of parameters
0x01
1 parameter
4
Format
0x43
Parameter format: Double word
5
No. of values
0x01
1 value
6, 7
Value Hi
0x311C
Higher-order part of the parameter
8, 9
Value Lo
0x7289
Lower-order part of the parameter
Decoding:
0x 311C 7289 = 823947913 dec
>> firmware version 823 947 9.13
0
0
I