OPERATION
No. Module Name
Data type Function
Comment
10
OUTPUT2_
CONTROL
Byte 1
Bit definition:
The function of the INPUTS / OUTPUTS can be
set in bus operation by using the respective mo-
dule. Otherwise, the functionality on delivery is
applicable.
0-3
Output function
0000 OFF
0001 Operational
0010 Pump active
0011 Stroke signal
0100 Pre-alarm level
0101 Dry run
0110 Diaphragm rupture
0111 No flow
1000 Group signal
1001 Group fault
1010 Internal error
1011 Batch finished
4.
NC contact / NO contact
11
A_OUTPUT_
CONTROL
Byte 1
Bit definition:
0-1
Analogue output function
00
Analogue input
01
Remaining batch
10
Stroke frequency / litre
capacity
2.
Reserved
3-4
Analogue output signal
00
0-20 mA
01
4-20 mA
10
Standardisation
Byte 2
Analogue output current 1
Bytes 2-5 are only used standardised for ana-
logue signal.
0= 0.0 mA
200= 20.0 mA
155= 15.5 mA
0-200
Byte 3
Analogue output percentage value
1
0-100%
Byte 4
Analogue output current 2
0-200
Byte 5
Analogue output percentage value
2
0-100%
12
MBE_CONTROL
Byte 1
Bit definition:
0-1
MBE signal
00
OFF
01
NC contact
10
NO contact
Byte 2
Sensitivity
0-100%