18
www.sera-web.com
OPERATION
No. Module Name
Data type Function
Comment
4
ANALOG_
CONTROL
Byte 1
Bit definition:
INPUT2_CONTROL or INPUT3_CONTROL
must be set as analogue input for the analogue
operation.
0-2
Analogue signal
00
0-20 mA
01
4-20 mA
10
Standardised
Byte 2
Analogue I1
Bytes 2-5 are only used standardised for ana-
logue signal.
0= 0.0 mA
200= 20.0 mA
155= 15.5 mA
0-200
Byte 3
Analogue Frequency f1
0-100%
Byte 4
Analogue I2
0-200
Byte 5
Analogue Frequency f2
0-100%
5
BATCH_CONTROL
Byte 1
Bit definition:
The remaining batch quantity is zeroed while
Bit 1 is set. Can also be used for cancellation of
a batch. Batch is also reset by setting External
Stop.
Two analogue inputs must be parametrised ac-
cordingly for Analogue Batch. The batch can be
started either by Bit 0 in Batch Control or by the
digital input.
Batch Flow = 0.0 can be set to pause a batch.
The speed can be varied during a batch.
0.
Start Batch
1.
Reset of the remaining
batch
2.
Normal batch / Analogue
batch
Float 2
Batch Volume
0.000 l - dependent on pump
Float 3
Batch Flow
not calibrated:
0.0 - 100.0%
calibrated:
0.000 l - max. litres/hour
6
INPUT1_CONTROL Byte 1
Bit definition:
The function of the INPUTS / OUTPUTS can be
set in bus operation by using the respective mo-
dule. Otherwise, the functionality on delivery is
applicable.
0-3
Input function
0000 OFF
0001 External stop
0010 Venting
0011 Impulse
0100 Analogue changeover
0101 Recipe
0110 Start Batch
4.
NC contact / NO contact