Measuring Compensated Liquid via a Turbine Meter
Best Practices
The Scanner 3300 calculates temperature- and pressure-compensated liquid flow through outputs from a MVT connected
to a turbine meter (or directly from the output from the turbine meter) in accordance with API MPMS Ch. 11.1 and the
measurement principles upon which the AGA 7 standard is based. When you supply a linear or multipoint calibration
factor, the instrument performs the required compensation calculations based on the RTD and/or pressure inputs.
For optimum performance, ensure that the turbine and MVT installation complies with the industry recommendations
listed below:
•
Install the turbine flowmeter in the meter run such that there are at least 10 nominal diameters of straight pipe
upstream and 5 nominal diameters of straight pipe downstream of the meter. Both inlet and outlet pipe should be of
the same nominal size as the meter.
•
Straightening vanes are recommended for eliminating swirl conditions. If used, they should be installed 5 diameters of
straight pipe upstream of the meter. If a pressure transducer is installed, it is recommended that it be placed upstream
of the flow straightener.
48
Section 2
Scanner 3300 EFM
Summary of Contents for 3300 EFM
Page 6: ...This page intentionally left blank v Scanner 3300 EFM Table of Contents...
Page 25: ...This page intentionally left blank 19 Scanner 3300 EFM Section 1...
Page 55: ...This page intentionally left blank 49 Scanner 3300 EFM Section 2...
Page 68: ...This page intentionally left blank 62 Section 3 Scanner 3300 EFM...
Page 76: ...This page intentionally left blank 70 Section 4 Scanner 3300 EFM...
Page 80: ...This page intentionally left blank 74 Section 5 Scanner 3300 EFM...
Page 84: ...This page intentionally left blank 78 Section 6 Scanner 3300 EFM...
Page 87: ...This page intentionally left blank A 3 Scanner 3300 EFM Appendix A...
Page 91: ...This page intentionally left blank B 4 Appendix B Scanner 3300 EFM...
Page 93: ...This page intentionally left blank C 2 Appendix C Scanner 3300 EFM...
Page 95: ...This page intentionally left blank C 4 Appendix C Scanner 3300 EFM...
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......