Introduction

The self-check UV Scanner is used for continuous gas or
oil flames. A mechanical shutter in the scanner closes
briefly every ten seconds, at which time the scanner’s
internal circuit checks for a flame signal. If a signal is
present, indicating a failed sensor, the output signal to the
flame safeguard is stopped and the system shuts down.
The scanner features a high quality fused silica quartz
lens, machined alloy housing with seals and a long life
push-pull electromagnetically driven photo shutter. This
scanner operates with the series 5600 and VF56 series
Veri-Flames, the series 6000 Multi-Flame, Series 6500 Bi-
Flame controllers, and series 7000 Peek-A-Flame.

Factory Mutual (FM) recommends these scanners be
used when any fired equipment is operated continuously
(more than 24 hours without shutdown).

Mechanical Specifications

Parameter

Specification

Overall Length

7-3/4" (197mm)

Diameter

3-1/4" (83mm)

Housing Material

Aluminum

Finish

Clear anodized

Sight Tube Entrance 1" NPT

Purge Air Entrance

1/4" NPT

Purge Air Flow

5 cfm, 10 psi maximum (140 
lpm, 0.7mbar)

Eclipse Self-Check

UV Scanner

Model

 

5602-91

856 Instruction Manual 

10/18/2010

Version 1

Summary of Contents for 5602-91

Page 1: ...ctromagnetically driven photo shutter This scanner operates with the series 5600 and VF56 series Veri Flames the series 6000 Multi Flame Series 6500 Bi Flame controllers and series 7000 Peek A Flame Factory Mutual FM recommends these scanners be used when any fired equipment is operated continuously more than 24 hours without shutdown Mechanical Specifications Parameter Specification Overall Lengt...

Page 2: ...ply NOTE The shield wire terminals shown in the tables provide a convenient attachment point A panel ground wire must also be run to these points Cable lead B should only be connected to power 120 VAC connecting it to any other terminal will bypass the safe start check of the scanner Parameter Specification Supply Voltage 120V 10 15 50 60 Hz Supply Current 0 04A Output Pulse frequency modulated tr...

Page 3: ...ure is 60 psig To assist in sighting the scanner a swivel mount 10042584 may be used Keep the scanner lens and line of sight free of contamination Be aware that scanners looking up are susceptible to dirt and dust settling Soot steam and unburned hydrocarbons may reduce or even mask the radiation from the flame A purging assembly as described above may alleviate these problems Some burners have an...

Page 4: ...ain flame trial for ignition smoothly restore the fuel supply to the main burner If the main burner does not light within five seconds immediately shut off the burner fuel supply stop the control and purge the system Attempt to light the burner again before proceeding with adjustments in the next step 8 For burners with an adjustable scanner sighting assembly adjust the sighting assembly further a...

Page 5: ...m and correct it before resuming normal operation Process Conditions Test 1 Start the system normally 2 Observe the flame signal as the system operates at various firing rates under process at temperature conditions 3 Perform the Main Flame Failure Test under these conditions and verify that the control shuts down in less than 4 seconds after visually observing that the flame extinguished Limit In...

Page 6: ...856 Instruction Manual 10 18 2010 Dimensions in inches mm 1 7 43 2 1 NPT INTERNAL 1 4 18 NPT 1 3 8 18 EXT Ø3 2 81 3 Ø2 0 50 8 7 5 190 5 6 8 172 7 1 8 45 7 ...

Reviews: