www.blazecut.com
Page 91 of 93
ILP CLEAN AGENT MANUAL-ILPCAM1904
BlazeCut and the BlazeCut logo are the registered trademarks of BlazeCut
© 2019 BlazeCut, All rights reserved
After finishing the pressurization close the valve of the charging
adapter.
Remove the charging adapter and close the filling port. The charging
valve in the charging portof the remote actuator will automatically
close.
Pressurization of the LOP line with charging adapter
Pressurize the LOP line correctly. If the pressure in it is lower than the pressure in the cylinder, the
valve piston of the cylinder could open and the extinguishing agent could be released when opening
the ball valve of the LOP line.
After pressurization observe the data on the pressure gauge.
If the pressure does not decrease, very slowly start opening the ball valve of the valve of the cylinder. The
pressures in the LOP line and in the cylinder will equalize. Wait approximately 30 seconds and open the ball valve
fully. In case of multiple cylinder connection open the ball valve on all valves of the cylinders.
From this moment the cylinder and the LOP line are connected into one pressure unit. Proceed further
carefully not to damage the BlazeTube detection. Its accidental damaging would activate the system
and release extinguishing agent.
Fast and careless opening of the ball valve may activate the system and release extinguishing agent.
Always place the remote actuator in the proximity of the protected enclosure so that it is easily accessible when
necessary. Do not place it in the area of expected fire, where manual activation after the fire has started is not
possible.
Label the remote actuator visibly with corresponding label ALA007.
Do not manually activate the system without reason. Use manual activation only in case of reasonable
suspicion of fire in the protected enclosure.
Do not manually activate the system if persons are present in the protected enclosures.
4.3.
REPLACEMENT OF THE MEMBRANE OF THE REMOTE ACTUATOR
After each use of the remote actuator the membrane of the remote actuator must be replaced as it is always
damaged during use. The replacement of the membrane is shown in the figures below:
S1. Disconnect the remote actuator from the LOP line and pull the pin.