ILP CLEAN AGENT MANUAL-ILPCAM1904
BlazeCut and the BlazeCut logo are the registered trademarks of BlazeCut
© 2019 BlazeCut, All rights reserved
releasing the extinguishing agent. This is the same process as during disruption of the BlazeTube detection by
effect of fire or heat.
CRA203 type: for bulkead mount
CRA204: on wall mount with additional M10x1 outlet.
It also serves as an end of line device of the BlazeTube detection. Any instruction in this manual regarding the
ending of the BlazeTube detection apply to manual actuator.
LHD BlazeWire - LHD BlazeWire works only in connection with the Alarm Panel AAP200/CAP200 or fire panels
and can be supplied with various activation temperatures depending on type of application.
Relay based smoke and heat detectors: ASD001 (smoke detector), AHD002 (heat and smoke detector), AHD001
(heat detector differential).
Remote electric actuators – CRA104 (yellow), CRA105 (blue), CRA106 (red).
INSTALLATION OF THE SYSTEM WITHOUT THE BLAZETUBE DETECTION (ONLY SYSTEMS
CEA(FA,NO)10
Some applications require installation without the BlazeTube detection. In these cases the activation of the
system has to be secured by different method e.g. manually by using electric signal from alarm panel,
automatically by using the LHD BlazeWire, detectors etc. Due to these reasons it is possible to install the system
without the BlazeTube detection only with the valve type 10 with integrated solenoid, systems CEA(FA,NO)10.
In this case the outlet of the BlazeTube detection and the ball valve of the valve of the cylinder is dismounted
and opening on the valve is sealed by a sealing screw or the BlazeTube detection outlet is replaced with additional
M10x1 adaptor.
Never dismount a sealing screw closing the opening of the outlet of the BlazeTube detection. Its
removal would cause immediate opening of the piston of the cylinder and release of the extinguishing
agent.
If the BlazeTube detection is not installed, procedures to the BlazeTube detection and outlet of the BlazeTube
detection mentioned in this manual are not applicable.
Without the BlazeTube detection it is not possible to install the system by using optional components: Remote
actuator CRA203 and CRA204 and Solenoid valve CSV001 as these components require the BlazeTube detection
for operation.
INSTALLATION OF THE SYSTEM WITH THE BLAZETUBE DETECTION OUTSIDE THE PROTECTE D
ENCLOSURE
In some cases use of the BlazeTube detection for fire detection is not suitable but can be useful to activate the
system for example manually by using remote actuator or end of line solenoid valve (through alarm panel or
detector).
In this case the BlazeTube detection is not installed in the protected enclosure and is not used for fire detection.
It is only conducted from the valve to remote actuator CRA203 or CRA204 or solenoid valve CSV001 to place of
operation of the system.
In harsh environment or high vibration installations the outlet of the BlazeTube detection on the valve, remote
actuator and end of line solenoid valve can be factory adjusted to fit the LOP hose of same construction and
material as feed hose or distribution hose. LOP hose has higher durability against mechanical damage compare
to BlazeTube detection.
All instructions in regards to the BlazeTube detection, its installation and pressurization in this manual remain in
reasonable force.