www.blazecut.com
Page 47 of 93
ILP CLEAN AGENT MANUAL-ILPCAM1904
BlazeCut and the BlazeCut logo are the registered trademarks of BlazeCut
© 2019 BlazeCut, All rights reserved
The system may be installed, maintained and repaired only by persons trained or authorized by the
manufacturer and depending on procedure also with relevant professional qualification.
Unprofessional interference with the system may cause malfunction of the system and provides
danger to safety and health of people.
When handling parts of the system under pressure (cylinder, valves, pressure switch, BlazeTube
detection) always wear appropriate protective glasses with side-shields. Eyes may be seriously
damaged when coming into contact with extinguishing agent in case of sudden leak.
If leak of liquid extinguishing agent occurs, always prevent contact with skin. Use suitable
impermeable protective work gloves.
During installation and maintenance of systems with HFC gaseshave appropriate detection device for
inspection of HFC gases used in system BlazeCut leak available at all times.
Refrain from handling the system, if it was exposed high temperature (as a result of operation of the
protected device or after exposure to fire etc.). If the system is hot, temperature of extinguishing
agent increases and pressure in the system increases. In this case the BlazeTube detection cannot be
put under mechanical stress. Splashing of hot extinguishing agent under high pressure may cause
serious injury. Wait until the system cools off naturally.
6.2.
INSTALLATION AND PLACEMENT OF THE CYLINDER
In order to release the extinguishing agent by pressure, there is a dip tube in the cylinder. This is why the cylinder
must be installed in vertical position. If the cylinder is leaning the extinguishing agent is not fully released as the
level of extinguishing agent decreases under the end of the dip tube.
If the installation of the cylinder is necessary in other than vertical position due to shape of the protected
enclosure, contact the supplier of the system before the purchase. In this case it is possible to customize the dip
tube (customization however, is not possible after closing of the cylinder by the valve).
The cylinder should be placed as close to the protected area as possible, so that the distribution tubes and the
BlazeTube detection can be as short as possible. If the cylinder is placed directly into the protected area, the
cylinder should be protected if necessary.
The cylinder should be placed so that the cylinder label is visible and the current pressure can be read on the
pressure gauge (if it is kept at the valve of the cylinder).
Use only undamaged cylinder filled with the correct extinguishing agent, properly labeled, with properly
mounted valve of the cylinder. Cylinder is supplied pressurized to required pressure. Current pressure can be
determined by reading the value on the pressure gauge, which is mounted on the valve of the cylinder when the
system is supplied.
Cylinder positioning
1. Extinguishing agent
2. Dip tube