SYSTEMS WITH EXTINGUISHING AGENT NOVEC 1230 (FK-5-1-12) USED - CNO10(35)
Extinguishing agent in the cylinder is in liquid form. The cylinder is pressurized with nitrogen gas under pressure
of 15 bar at temperature 20° C.
The relationship between temperature and pressure in the cylinder:
WARNINGS
In case of a significant difference between the actual pressure in the system with the data in the table,
ensure inspection of the system.
Do not install the cylinder into the configuration, if incorrect pressure is detected in the cylinder during
inspection (i.e. pressure is significantly different from the values stated above).
The cylinder of the system is under constant pressure. Do not damage the cylinder, do not puncture
or throw. During transportation secure against tipping and movement. During transfer do not roll or
rub against the ground. Do not mend or solder damaged cylinder. During storage separate empty
cylinders from full ones and mark the storage place. Do not store or transportation in vicinity of strong
sources of heat, aggressive chemical substances (caustic, corrosive substances), prevent contact with
sharp objects, vibrations or loading with other objects. Store in dry and well ventilated rooms.
Do not expose the cylinder to direct sunlight. Heating the surface of the cylinder may significantly
increase pressure in the cylinder.
Always handle the cylinder as if it were under pressure, unless it is directly verified that it is completely
empty (e.g. by pressing the filling valve in the M10x1 pressure gauge outlet on the valve of the
cylinder; the value of the pressure on the pressure gauge may be incorrect or the pressure gauge may
be malfunctioning).
Transportation of equipment under pressure and equipment containing HFC gases by transportation
vehicles is governed by specific legislation. Seek information and follow corresponding security
requirements during transportation depending on the method of transport.
3.2.
VALVE OF THE CYLINDER
Valve of the cylinder is part of the cylinder when system BlazeCut is supplied. The valve is closed by a piston,
which keep the pressure in the system. The piston opens with rapid decrease of pressure or with electric
activation using solenoid.
5
10
15
20
25
30
-40
-20
0
20
40
60
80
100
120
pr
ess
ur
e
(ba
r)
temperature (°C)
Novec 1230