Cylinders are situated on opposite sides of
the protected enclosure. This method is
suitable when larger space needs to be
protected, for example the protected
enclosure is long (shafts etc.).
1. Cylinder with the valve
2. Protected enclosure
3. BlazeTube detection
4. Tee connection
5. End of line device
BlazeTube installation limits in single and multiple cylinders configurations
Single cylinder
Type of valve
Maximum Length of BlazeTube (m)
10
40
35
40
Multiple cylinder / Electronic actuation and BlazeTube in protected enclosure
Configuration of valves
Maximum Length of BlazeTube (m)
10 x 35
15
10 x 35 x 35
15
10 x 35 x 35 x 35
10
10 x 35 x 35 x 35 x 35
10
10 x 35 x 35 x 35 x 35 x 10*
10
Multiple cylinders / LOP actuation with BlazeTube in protected enclosure
Configuration of valves
Maximum Length of BlazeTube (m)
35 x 35
40
35 x 35 x 35
40 in loop
35 x 35 x 35 x 35
40 in loop
35 x 35 x 35 x 35 x 35
40 in loop
35 x 35 x 35 x 35 x 35 x 35
40 in loop
*Note: Maximum multiple cylinders configuration using the solenoid require two 10 series valves
situated as first and last valve in the multiple cylinders configuration.
6.5.
PRESSURIZATION OF THE BLAZETUBE DETECTION SYSTEM
The BlazeTube detection must be pressurized with correct pressure by nitrogen gas (N
2
) before the system is put
into operation. Use appropriate source N
2
- cylinder with control valve. The tube must be pressurized with the
same pressure as the pressure in the cylinder.
Pressurization is performed through the end of line device of the
BlazeTube detection using charging adapter ATC001. The BlazeTube
detection end of line devices have outlet with thread M10x1 and contains
filling valve, which must be pushed and open with the charging adapter.
This valve closes and opens automatically during removal or installation
of the charging adapter or the pressure gauge. It is possible to install and
remove these components even when the tube is under pressure.
Before pressurization of the tube make sure that the ball valve is closed.
Tool charging adapter