END OF LINE ADAPTER
BlazeTube end of line adapter is used for pressurization of the BlazeTube detection system when the system is
installed (see Chapter 6.4.) and for pressurization of the system during inspection (see Chapter 6.5.).
Part No.
Description
Thread
CEA006
End of line adapter Ø 6 mm with push in fitting
for BlazeTube
M10x1 to connect the pressure gauge or
pressure switch/transducer
END OF LINE PLUG
End of line plugs are used to close one of the BlazeTube detection’s when branching the BlazeTube.
Part No.
Description
CBTF006
Push in end of line plug Ø 6 mm
3.7.
BLAZEWIRE
BlazeWire Overview
BlazeWire Linear Heat Detector is a cable constructed using two twisted and tensioned, tri-metallic conductors.
Each of the conductive cables are coated in a heat sensitive polymer which, when heated to its rated
temperature, melts, causing the
two cables to touch. The resulting
short sends a signal to the alarm
panel, indicating tahat a fire (or
excessive heat) has been detected.
This action takes place at the first
heated point anywhere along the
BlazeWire’s length, which can be up
to 50 metres. It does not require
that a specific length be heated in order to initiate an alarm nor is system calibration necessary to compensate
for changes in the installed ambient temperature.
CBTF006
End of line adapter CEA006
Pressure Switch APS001 fitted on the End of
line adapter CEA006