SENS MicroGenius S2/S4 Technical Manual
52
Address High
Address Low
Name
Description
Units
Scale
Voltage Setting
606
0x25E
607
0x25F Output C Battery Check
Interval
Interval between scheduled
automatic battery checks
Days
86400
608
0x260
609
0x261 Output C Battery Check
Duration
Duration of battery check
Min
60
610
0x262
611
0x263 Output C Default Output
Commissioning VPC
Commissioning VPC
V/Cell
32768
612
0x264
613
0x265 Output C Default Output
Commissioning Duration
Commissioning Duration
Hr
3600
614
0x266
615
0x267 Output C Default Output
Commissioning A
Commissioning Amps
A
32768
616
0x268
617
0x269 Output C Default Output
Rated Power
Output Rated Power
W
32768
618
0x26A
619
0x26B Output C Default Output
Rated Current
Output Rated Current
A
32768
620
0x26C
621
0x26D Output C Periodic Boost
Duration
Periodic Boost Duration
Bits
3600
622
0x26E
623
0x26F Channel C Min Allowed
Voltage Setting
Min Allowed Voltage Setting
V/Cell
32768
640
0x280
641
0x281 Output D Status
Current State of the charger (see
section 11.3)
Bits
1
642
0x282
643
0x283 Output D Alarms
Alarm status bits (see section 11.4)
Bits
1
644
0x284
645
0x285 Output D Voltage
Voltage currently being supplied by
the charger to the battery
V
32768
646
0x286
647
0x287 Output D Output Current
Current currently being supplied by
the charger to the battery
A
32768
648
0x288
649
0x289 Output D Power Output
Power currently being supplied by
the charger
W
32768
650
0x28A
651
0x28B Output D Factory Float
Setting
Float Cell Voltage set at Factory
V/cell
32768
652
0x28C
653
0x28D Output D Factory Boost
Setting
Boost Cell Voltage set at Factory
V/cell
32768
654
0x28E
655
0x28F Output D Remote Temp
Remote temp sense temperature in
0.0°C
°C
32768
656
0x290
657
0x291 Output D Internal Temp
Ambient air temperature near
charger input connectors (tp 1)
°C
32768
658
0x292
659
0x293 Output D Boost Elapsed
Time
Boost time
Sec
1
660
0x294
661
0x295 Output D Periodic Boost
Period
Interval between periodic boost
events (0 = disabled)
Sec
1
662
0x296
663
0x297 Output D AC Line
Frequency
AC Line Frequency
Hz
10
664
0x298
665
0x299 Output D AC Line Voltage 1 AC Line 1 Voltage
V
32768
666
0x29A
667
0x29B Output D AC Line Current 1 AC Line 1 Current
A
32768
668
0x29C
669
0x29D Output D AC Line Voltage 2 AC Line 2 Voltage (Not applicable to
single phase chargers)
V
32768
670
0x29E
671
0x29F Output D AC Line Current 2 AC Line 2 Current (Not applicable to
single phase chargers)
A
32768
672
0x2A0
673
0x2A1 Output D AC Line Voltage 3 AC Line 3 Voltage (Not applicable to
single phase chargers)
V
32768
674
0x2A2
675
0x2A3 Output D AC Line Current 3 AC Line 3 Current (Not applicable to
single phase chargers)
A
32768
676
0x2A4
677
0x2A5 Output D Battery Check
Duration
Duration of battery check
Sec
1