SENS MicroGenius S2/S4 Technical Manual
27
8.4.3.
Battery Discharging
Indicates battery is beginning to discharge and DC output voltage is below factory alarm setpoint
(see Table 13) or the configured level if setpoint is adjusted using keypad or SENS Setup Utility.
The BATTERY DISCHARGING alarm is the first to trigger of three low output voltage alarms and is
followed by LOW DC and then END OF DISCHARGE. Alarm setpoint must be set higher than LOW
DC and END OF DISCHARGE alarms. Activates solid yellow DC LED. Alarm/communications circuit
board BATTERY DISCHARGING relay contacts change to Fail state after delay when alarm is
assigned to relay contacts.
Table 13 – Factory Battery Discharging Setpoints
Configuration
Code*
Battery Type
Battery Discharging Setpoint
12V
24V
GEN
AGM
12.50
25.00
FLA
12.50
25.00
NCD
12.50
25.00
HCB
12.50
25.00
Ultracapacitor
14.40
24.00
MAR
VRLA
12.00
24.00
AGM
12.00
24.00
NCD
12.00
24.00
NGN
VRLA
12.00
24.00
AGM
12.00
24.00
NCD
12.00
24.00
PSP
N/A
10.20
20.40
*Configuration Code displayed on charger label.
8.4.4.
Low DC Voltage
Indicates battery has discharged and DC output voltage is below factory alarm setpoint (see Table
14) or the configured level if setpoint is adjusted using keypad or SENS Setup Utility. Alarm
setpoint must be set lower than BATTERY DISCHARGING and higher than END OF DISCHARGE
alarms. Activates solid yellow DC LED. Alarm/communications circuit board LOW DC relay
contacts change to Fail state after delay when alarm is assigned to relay contacts.
Table 14 – Factory Low DC Setpoints
Configuration
Code*
Battery Type
Low DC Setpoint
12V
24V
GEN
AGM
12.10
24.20
FLA
12.10
24.20
NCD
12.10
24.20
HCB
12.10
24.20
Ultracapacitor
13.00
22.40
MAR
VRLA
11.00
22.00
AGM
11.00
22.00
NCD
11.00
22.00
NGN
VRLA
11.00
22.00
AGM
11.00
22.00
NCD
11.00
22.00
PSP
N/A
10.20
20.40
*Configuration Code displayed on charger label.