SENS MicroGenius S2/S4 Technical Manual
39
output models
DC Output #D
Enable or disable output D for multiple
output models
Set Output
Assign charger modules to each S2/S4 output
for multiple output models
Battery Check
Select DC Output
(multiple output
models only)
Select output to adjust specific settings
Battery Check
Start or stop a manual Battery Check.
Batt Check Time
Adjust amount of time to run Battery Check
from 1 to 60 minutes
Batt Check Vmin
Adjust minimum voltage allowed during
Battery Check test, must be greater than
End-of-Discharge voltage and less than 98%
Float voltage
Sched Batt Check
Adjust amount of time between scheduled
Battery Check tests from 1 to 90 days
Next Sched Batt Check
View time until next scheduled Battery
Check test
Service Tools
Relay Test
Press UP arrow to set all alarm relays and
DOWN arrow to clear all relays
Display Test
Press UP arrow to set all LCD segments black
and DOWN arrow to clear all LCD segments
Check Vent Fan
Press UP arrow to run vent fan and DOWN
arrow to stop vent fan.
Available on
MicroCab units only.
Internal Voltages
View internal rail voltages for
troubleshooting purposes. Correct values are
approximately 3.3V, 5V and 11V.
UI Access Control
Select allowed user interface access. Access
options include read-only viewing, normal
access or full access adjustments for
advanced users.
Change Security Code
Change security code to desired 6 digits. The
default security code is 000000 (disabled).
Upon entering a security code, the display
will automatically prompt user for the code
to access protected menus. Menus are
protected depending on configured level of
access (see UI Access Control definitions
above).
Relock Access
Exit Service Mode and relock access
I-O Bus Settings
I-O Configuration
Select RTU or ASCII Modbus (RS-485). Set to
OFF to disable Modbus communications.
I-O Configuration I-O Address
Adjust Modbus slave address from 1 to 255
(RS-485). Set to OFF to disable Modbus
communications.
I-O Configuration Parity Bit
Set Modbus (RS-485) parity to none, even or
odd
I-O Configuration Baud Rate
Adjust Modbus (RS-485) baud rate, 57.6
Kbps maximum
Modbus Configuration Write
Enable or disable write access via Modbus
J1939 Configuration BCH1 Output
Assign charger output for J1939 battery
charger address to 1. J1939 address 1 (main
charger) is assigned to charger output A by
default.
Not available on MicroCab units.