SENS MicroGenius S2/S4 Technical Manual
51
Address High
Address Low
Name
Description
Units
Scale
528
0x210
529
0x211 Output C AC Line Voltage 3 AC Line 3 Voltage (Not applicable to
single phase chargers)
V
32768
530
0x212
531
0x213 Output C AC Line Current 3 AC Line 3 Current (Not applicable to
single phase chargers)
A
32768
532
0x214
533
0x215 Output C Battery Check
Duration
Duration of battery check
Sec
1
534
0x216
535
0x217 Output C Battery Check
Interval
Interval between scheduled
automatic battery checks
Sec
1
536
0x218
537
0x219 Output C Number of
Chargers
Number of chargers detected on
SENSbus, 0 - 30
Num
1
538
0x21A
539
0x21B Output C Redundancy Level Number of redundant output
chargers
Num
1
540
0x21C
541
0x21D Output C Extended Status
Current state of alarm/comms circuit
board (see section 11.5)
bit
1
560
0x230
561
0x231 Output C Maximum Power Maximum rated power
V/Cell
32768
562
0x232
563
0x233 Output C Maximum Voltage Maximum rated voltage in x.xx V
V/Cell
32768
564
0x234
565
0x235 Output C Maximum Current Maximum rated current in x.xxA
A
32768
566
0x236
567
0x237 Output C Program Float
Setting
Float Cell Voltage used in Program
Mode
V/Cell
32768
568
0x238
569
0x239 Output C Program Boost
Setting
Boost Cell Voltage used in Program
Mode
V/Cell
32768
570
0x23A
571
0x23B Output C Program Mode
Mode callouts for Program Mode
setting (battery type… etc.)
Custom
1
572
0x23C
573
0x23D Output C Program Cell
Count
Number of cells set in Program Mode
Cells
32768
574
0x23E
575
0x23F Output C Program Temp
comp slope
In 0.xx°C per output volt x -1
°C/V
32768
576
0x240
577
0x241 Output C Low DC Program Alarm setpoint for low DC (used for
Program Mode setting)
V/Cell
32768
578
0x242
579
0x243 Output C Low Crank
Program
Alarm setpoint for low Crank (used
for Program Mode setting)
V/Cell
32768
580
0x244
581
0x245 Output C Low Current
Program
Alarm setpoint for low Current(used
for Program Mode setting)
A
32768
584
0x248
585
0x249 Output C High DC Program Alarm setpoint for high DC (used for
Program Mode setting)
V/Cell
32768
586
0x24A
587
0x24B Output C OVSD Program
Alarm setpoint for OVSD (used for
Program Mode setting)
V/Cell
32768
588
0x24C
589
0x24D Output C Batt Discharge
Program
Alarm setpoint for Batt Discharge
(used for Program Mode setting)
V/Cell
32768
590
0x24E
591
0x24F Output C Batt End
Discharge Program
Alarm setpoint for End Discharge
(used for Program Mode setting)
V/Cell
32768
592
0x250
593
0x251 Output C Program Boost
Time Limit
Boost time limit (used for Program
Mode setting)
Hr
3600
594
0x252
595
0x253 Output C Current Limit
Setting
Current Limit setpoint in % of output
current as a 10 bit value
% Rated
A
32768
596
0x254
597
0x255 Output C Default Output
Helix Float Time
Helix Float Time
Hr
3600
598
0x256
599
0x257 Output C Default Output
Helix Refresh Time
Helix Refresh Time
Hr
3600
600
0x258
601
0x259 Output C Default Output
Helix Eco Time
Helix Eco Time
Hr
3600
602
0x25A
603
0x25B Output C Default Output
Periodic Boost Time
Interval between scheduled Periodic
Boost
Days
86400
604
0x25C
605
0x25D Output C Battery Check
Battery check failure threshold
V/Cell
32768