SENS MicroGenius S2/S4 Technical Manual
47
Address High
Address Low
Name
Description
Units
Scale
228
0x0E4
229
0x0E5 Output A Periodic Boost
Period
Interval between periodic boost
events (0 = disabled)
Sec
1
230
0x0E6
231
0x0E7 Output A AC Line
Frequency
AC Line Frequency
Hz
10
232
0x0E8
233
0x0E9 Output A AC Line Voltage 1 AC Line 1 Voltage
V
32768
234
0x0EA
235
0x0EB Output A AC Line Current 1 AC Line 1 Current
A
32768
236
0x0EC
237
0x0ED Output A AC Line Voltage 2 AC Line 2 Voltage (Not applicable to
single phase chargers)
V
32768
238
0x0EE
239
0x0EF Output A AC Line Current 2 AC Line 2 Current (Not applicable to
single phase chargers)
A
32768
240
0x0F0
241
0x0F1 Output A AC Line Voltage 3 AC Line 3 Voltage (Not applicable to
single phase chargers)
V
32768
242
0x0F2
243
0x0F3 Output A AC Line Current 3 AC Line 3 Current (Not applicable to
single phase chargers)
A
32768
244
0x0F4
245
0x0F5 Output A Battery Check
Duration
Duration of battery check
Sec
1
246
0x0F6
247
0x0F7 Output A Battery Check
Interval
Interval between scheduled
automatic battery checks
Sec
1
248
0x0F8
249
0x0F9 Output A Number of
Chargers
Number of chargers detected on
SENSbus, 0 - 30
Num
1
250
0x0FA
251
0x0FB Output A Redundancy Level Number of redundant output
chargers
Num
1
252
0x0FC
253
0x0FD Output A Extended Status
Current state of alarm/comms circuit
board (see section 11.5)
bit
1
272
0x110
273
0x111 Output A Maximum Power Maximum rated power
V/Cell
32768
274
0x112
275
0x113 Output A Maximum
Voltage
Maximum rated voltage in x.xx V
V/Cell
32768
276
0x114
277
0x115 Output A Maximum
Current
Maximum rated current in x.xxA
A
32768
278
0x116
279
0x117 Output A Program Float
Setting
Float Cell Voltage used in Program
Mode
V/Cell
32768
280
0x118
281
0x119 Output A Program Boost
Setting
Boost Cell Voltage used in Program
Mode
V/Cell
32768
282
0x11A
283
0x11B Output A Program Mode
Mode callouts for Program Mode
setting (battery type… etc.)
Custom
1
284
0x11C
285
0x11D Output A Program Cell
Count
Number of cells set in Program Mode
Cells
32768
286
0x11E
287
0x11F Output A Program Temp
comp slope
In 0.xx°C per output volt x -1
°C/V
32768
288
0x120
289
0x121 Output A Low DC Program Alarm setpoint for low DC (used for
Program Mode setting)
V/Cell
32768
290
0x122
291
0x123 Output A Low Crank
Program
Alarm setpoint for low Crank (used
for Program Mode setting)
V/Cell
32768
292
0x124
293
0x125 Output A Low Current
Program
Alarm setpoint for low Current(used
for Program Mode setting)
A
32768
296
0x128
297
0x129 Output A High DC Program Alarm setpoint for high DC (used for
Program Mode setting)
V/Cell
32768
298
0x12A
299
0x12B Output A OVSD Program
Alarm setpoint for OVSD (used for
Program Mode setting)
V/Cell
32768
300
0x12C
301
0x12D Output A Batt Discharge
Program
Alarm setpoint for Batt Discharge
(used for Program Mode setting)
V/Cell
32768
302
0x12E
303
0x12F Output A Batt End
Discharge Program
Alarm setpoint for End Discharge
(used for Program Mode setting)
V/Cell
32768
304
0x130
305
0x131 Output A Program Boost
Boost time limit (used for Program
Hr
3600