waterproof cable connectors and reserve appreciate wire length for wiring to the
inverter.
Figure 5.22
Processing RS485 cable
Step 4
Take out RS485 terminal block from accessary kit, remove the 4 screws from
its male terminal, and connect with RS485 cable, as shown in Figure 3.19
Figure 5.23
RS485 Terminal block connection
Step 5
Connect RS485 male terminal with its female terminal, shown as Figure 5.24.
Figure 5.24
RS485 cable connections
Step
Tighten the locking caps to a torque of 8 N·m as well as waterproof cable
connectors, as shown in 5.24.
43