Shutdown
The PV inverter switches from standby or operating mode to shutdown mode if
detecting a fault or a shutdown command.
The shutdown mode can only be cleared when rebooting DC side or receiving a
booting command.
3 Storage
This chapter describes the storage requirements for the inverter.
The following storage instructions apply if the PV inverter will not be deployed
immediately:
>Do not unpack the inverter (put desiccant in the original box if the PV inverter is
unpacked).
>Store the PV inverter at a temperature range of -40°C to +70°C and with the relative
humidity of 0% to 100% (no condensing).
>The PV inverter should be stored in a clean and dry place and be protected from dust
and water vapor corrosion.
>
A maximum of four layers of inverters can be stacked.
>
Do not position the inverter at a front tilt, excessive back tilt, or side tilt, or upside
down.
>Conduct periodic inspection during storage. Replace the packing materials
immediately if any rodent bites are found.
>
Ensure that qualified personnel inspect and test the inverter before use if it has been
stored for a long time.