Service settings manual
42
Para-
meter
Function
Parameter description
Setting range
Default
value
F2.18 SWITCH-ON DE-
LAY / CIRCULATI-
ON PUMP STANDBY
TIME
This function delays activation of output for setted time. Output is
activated when setted delay time expires.
REMARK: If delay time is longer as time of switch-on period the
output won't activate.
Setting 0 means there is no delay and the output should activate
immedately and stay activated for the whole time of switch-on com-
mand.
0 ÷ 3600 s
0
F2.19 MIN/MAX
TEMPERATURE
LIMITATION
Setting if controller should respect min. and max. temperature limita-
tions of certain sensor by control of output. This function is usefull by
thermostatic operation of output, where min. and max. temperature
limitations of particular sensor should also be respected.
0- NO
1- MIN OFF
2- MAX ON
3- MIN OFF & MAX
ON
4- MIN ON
5- MAX OFF
6- MIN ON & MAX
OFF
0
F2.20 SENSOR FOR MIN/
MAX TEMPERATU-
RE LIMITATION
Selection of sensor for the MIN/MAX limitation.
1- T1 5- T5
2- T2 6- T6
3- T3 7- T7
4- T4
5*
Table with description of parameters :
Para-
meter
Function
Parameter description
Setting range
Default
value
F3.1
OUTPUT PROGRAM-
MING
Selection of output for programming.
0- NO 4- R4
1- R1 5- R5
2- R2 6- R6
3- R3
0*
F3.2
DEPENDENCE TO
OTHER OUTPUTS
Define dependence of programmed output to other
controller's outputs.
&- selected relay has to be switched-on for programmed
output to be able to switch- on
&!- selected relay has to be switched-off for programmed
output to be able to switch- on
I- programmed output will switch-on always when se-
lected relay is switched-on
I!- programmed output will always switch- on when the
selected relay is switched-off
0- NO
1- &
2- &!
3- I
4- I!
0
F3.3
DEPENDENT OUTPUT Selection of output on which depends operation of
programmed output.
1- R1 4– R4
2- R2 5– R5
3- R3 6– R6
*
F3.4
TIME PROGRAM FOR
OUTPUT
Selection of required time program for programmed
output.
0- NO
1- P1
2- P2
3- P3
4- P4
5- SEL. PROG. TIMER
0
F3.5
THERMOSTATIC OPE-
RATION OF OUTPUT
Selection if programmed output operates as a thermostat. 0- NO
1- YES
2- YES, INVERTED
3- YES, AUX. SOURCE
4- YES, CASC. SOURCE
0
F3.6
TYPE OF AUXILIARY
HEAT SOURCE
Selection of type of heating source.
1- BURNER
2- EL. HEATER
3- HEAT PUMP
0
* Depends on the controller model.
Summary of Contents for SGC36
Page 2: ......
Page 4: ......
Page 137: ...137 TABLE 1 Factory settings of parameters P1 TABELLE 1 Werkseinstellungen vom Parametern P1...
Page 138: ...138 TABLE 2 Factory settings of parameters P2 TABELLE 2 Werkseinstellungen vom Parametern P2...
Page 139: ...139 TABLE 3 Factory settings of parameters P3 TABELLE 3 Werkseinstellungen vom Parametern P3...
Page 141: ...NOTES NOTIZEN 141...
Page 142: ...NOTES NOTIZEN 142...
Page 143: ......