Table with description of parameters :
Para-
meter
Function
Parameter description
Setting range Default
value
S1.1
HYDRAULIC SCHEME
Selection of hydraulic scheme.
depends on type
of controller
201
S1.2
CODE FOR UNLOCKING THE
SERVICE SETTINGS
This setting enables the change of code which is necessary
to unlock the service settings (S and F parameters).
WARNING! Keep new code on a safe place. Without this
code is impossible to change service settings.
0000 - 9999
0001
S1.3
TEMPERATURE SENSOR
TYPE
Selection of temperature sensors Pt1000 or KTY10.
0- PT1000
1- KTY10
0
S1.4
TEMPERATURE ROUND UP Precision of displayed temperatures.
0- 0.1 °C
1- 0.2 °C
2- 0.5 °C
3- 1 °C
2
S1.5
PERIOD OF TEMPERAT.
LOGGING
By setting this field you define how often the measured
temperatures are saved.
1 ÷ 30 min
5
S1.6
ADVANCED DISPLAY OF
TEMPERATURES
Advanced display of temperatures displays temperatures on
main screen in double rows. First row is measured tempera-
ture; second row is required or calculated temperature.
0- NO
1- YES
1
S1.7
AUT. SHIFT OF CLOCK TO
SUMMER / WINTER TIME
With the help of a calendar, the controller carries out the
automatic clock changeover between summer and winter
time.
0- NO
1- YES
1
S1.8
ANTI-BLOCK FUNCTION
All outputs that haven’t been activated in the last week are
activated on Friday at 20:00 for 60 seconds.
0- NO
1- YES
0
S1.9
INVERTED OPERATION OF
OUTPUTS
Setting of inverted operation for outputs. Invertion of output is
possible only if operation mode of output is ON/OFF
(S3.1=0).
0- NO
1- R1
2- R2
3- R1, R2
4- R2, R3
5- R1, R3
6- R2, R3
7- R1, R2, R3
0
S1.10
TONES
By setting this field you define whether key pressing is
accompanied with sound signals or not.
0- OFF
1- KEYPAD
2- ERRORS
3- KEYPAD &
ERRORS
1
S1.13
SENSOR T1 CALIBRATION Correction of displayed measured temperature for sensor T1. -5 ÷ 5 °C
0
S1.14
SENSOR T2 CALIBRATION Correction of displayed measured temperature for sensor T2. -5 ÷ 5 °C
0
S1.15
SENSOR T3 CALIBRATION Correction of displayed measured temperature for sensor T3. -5 ÷ 5 °C
0
S1.16
SENSOR T4 CALIBRATION Correction of displayed measured temperature for sensor T4. -5 ÷ 5 °C
0
S1.17
SENSOR T5 CALIBRATION Correction of displayed measured temperature for sensor T5. -5 ÷ 5 °C
0
S1.18
SENSOR T6 CALIBRATION Correction of displayed measured temperature for sensor T6. -5 ÷ 5 °C
0
S1.19
SENSOR T7 CALIBRATION Correction of displayed measured temperature for sensor T7. -5 ÷ 5 °C
0
Summary of Contents for SGC36
Page 2: ......
Page 4: ......
Page 137: ...137 TABLE 1 Factory settings of parameters P1 TABELLE 1 Werkseinstellungen vom Parametern P1...
Page 138: ...138 TABLE 2 Factory settings of parameters P2 TABELLE 2 Werkseinstellungen vom Parametern P2...
Page 139: ...139 TABLE 3 Factory settings of parameters P3 TABELLE 3 Werkseinstellungen vom Parametern P3...
Page 141: ...NOTES NOTIZEN 141...
Page 142: ...NOTES NOTIZEN 142...
Page 143: ......