Service settings manual
35
HEAT METERING PARAMETERS
The procedure for setting function parameters is the same as for service
parameters (see page 30).
Group W contains parameters to set the solar heat metering.
Para-
meter
Function
Parameter description
Setting range Default
value
S3.15
ACTUATOR RUNNING TIME Actuator running time, needed for a 90° turn. This data is
considered at delayed switchovers with valves.
1 ÷ 8 min
2
S3.16
BOILER CIRCULATION
PUMP - OPERATION MODE
This setting defines how boiler circulation pump shall operate:
1- STANDARD means that circulation pump is running ac-
cording to setted minimum boiler temperature and according
to temperature difference between return pipe and boiler
temperature.
2- ALWAYS means that circulation pump is running always
when boiler temperature is higher as setted minimum boiler
temperature. Such operation mode is used for systems of
pellet boiler without sensor in storage tank.
1- STANDARD
2- ALWAYS
1
S3.17
MIXING VALVE P - CON-
STANT
Setting of mixing valve position correction intensity. Smaller
value means shorter movements, higher value means longer
movements.
0,5 ÷ 2,0
1
S3.18
MIXING VALVE I - CON-
STANT
Setting of mixing valve control frequency - how often mixing
valve position is being controlled. Smaller value means low
frequency, higher value means higher frequency.
0,4 ÷ 2,5
1
S3.19
MIXING VALVE D - CON-
STANT
Sensitivity of mixing valve for stand-pipe temperature chan-
ges. Smaller value means low sensitivity, higher value means
high sensitivity.
0,0 ÷ 2,5
1
S3.20
BACKLASH OF MIXING
VALVE
Setting of mixing valve running time to compensate the bac-
klash of actuator and mixing valve assembly, which occours
by change of rotation direction.
0 ÷ 5 s
1
Summary of Contents for SGC36
Page 2: ......
Page 4: ......
Page 137: ...137 TABLE 1 Factory settings of parameters P1 TABELLE 1 Werkseinstellungen vom Parametern P1...
Page 138: ...138 TABLE 2 Factory settings of parameters P2 TABELLE 2 Werkseinstellungen vom Parametern P2...
Page 139: ...139 TABLE 3 Factory settings of parameters P3 TABELLE 3 Werkseinstellungen vom Parametern P3...
Page 141: ...NOTES NOTIZEN 141...
Page 142: ...NOTES NOTIZEN 142...
Page 143: ......