Service settings manual
27
Basic parameters are divided into groups P1, P2 and P3. In group P1 there are setting
for differences and hysteresis for built-in thermostats, in group P2 there are settings for
minimum and maximum temperatures for individual sensors, and controller performance
settings in group P3.
When selecting the required parameter group in the menu, a new window opens:
Parameter mark
Current parameter value
Diagram
of the setting
Factory value
The last confirmed
setting value
Current parameter value
Setting range
You modify the setting by pressing the button .
The value of setting starts to flash, and you can edit it by pressing buttons and
.
The setting is confirmed by pressing the button . Now you can move by pressing but-
tons and to another parameter and repeat the procedure.
You exit the parameter settings by pressing button .
All additional settings and adjustments of controller performance are carried out by means
of parameters. In controller parameter settings menu there are three selectable groups:
Basic parameters
Service parameters
Heat metering parameters
Parameters for free programming available outputs.
CONTROLLER PARAMETERS AND AUXILIARY TOOLS
BASIC PARAMETERS
Parameter
description
(Help)
SERVICE MANUAL
You can only see those parameters which have an effect on the selected hy-
draulic scheme. Factory settings for parameters also depend on the selected
hydraulic scheme.
Summary of Contents for SGC36
Page 2: ......
Page 4: ......
Page 137: ...137 TABLE 1 Factory settings of parameters P1 TABELLE 1 Werkseinstellungen vom Parametern P1...
Page 138: ...138 TABLE 2 Factory settings of parameters P2 TABELLE 2 Werkseinstellungen vom Parametern P2...
Page 139: ...139 TABLE 3 Factory settings of parameters P3 TABELLE 3 Werkseinstellungen vom Parametern P3...
Page 141: ...NOTES NOTIZEN 141...
Page 142: ...NOTES NOTIZEN 142...
Page 143: ......