LCQ / LCS / LCQI / BMQ / CPQ / TBQ / TBS / TBQI / TBSI EVAPORATIVE COOLER INSTALLATION MANUAL
|
15
ILL976-D
REFITTING THE PAD FRAMES
Refit the pad frames by locating the bottom edge in the tank
groove, then push the top into the lid.
TESTING THE PUMP
Test the pump by turning the cooler on at the controller, in
“COOL” mode. Check that water is evenly distributed to all
pads.
Note!
If the cooler has not been on before it will run a “Pre-Wet”
routine where the pump will operate to saturate the pads.
This cycle takes 2 minutes, then the fan will start automatically.
TESTING THE DRAIN VALVE
With the wall control in “OFF” mode, press and hold the
and
buttons together for 1 second on the MagIQcool
controller, “dr” is displayed and the drain valve will open.
Select the “SETTINGS” mode on the MagIQtouch Controller
and select the “COOLER” sub-heading. Select the “MANUAL
DRAIN” option to operate and test the drain valve.
COMMISSIONING COMPLETION CHECKLIST
COOLER
□ SECURE - The cooler is secure and level on the dropper
using all fixings supplied.
□ SEALED - The dropper and all penetrations are correctly
flashed and sealed.
AutoWinterseal
□ OPERATES - The AutoWinterseal operates correctly and can
open and close without interference.
PLUMBING
□ FLUSHED - The water pipes were flushed of any foreign
materials before connection to the cooler was made.
□ NO EXTERNAL LEAKS - The water is connected with no
leaks at fittings.
□ NO INTERNAL LEAKS - C
heck the internal water hose is
securely fitted to water distribution spreader on the lid and to
the pump.
□ SECURE - Water pipes are correctly saddled as per plumbing
regulations.
□ OWNER INSTRUCTIONS - The owner has been instructed
on how to isolate the water to the system in case of
emergency.
DRAIN VALVE
□ INSTALLED - The drain valve is installed correctly, as detailed
in this installation manual.
□ DISCHARGE - The drain water does not discharge onto the
roof surface.
□ WATER LEVEL - Water level has been set correctly, as
detailed in this installation manual.
□ TESTED - Drain the tank manually. Check the drain fittings
and pipes, making sure there are no leaks.
COMMISSIONING THE COOLER
cont
“A” Rebate
“B” Rebate
Drain Valve rebate
A
A
A
B
SUPERCOOL PAD POSITIONS
All Supercool Chillcel pads for LCS, TBS & TBSI coolers have
the side edges rebated to provide clearance for corner posts.
Note the position required for the pad with the Drain Valve (“B”
Rebate) rebate.
ILL2128-A
If fitted incorrectly they may cause problems:
• Thicker pads may catch on internal components causing
damage.
•
Thicker pads may impede the correct operation of the float
valve.
• Incorrect positioning of pads may cause a drop in cooler
performance.
•
Incorrect fitment may allow water to bypass the pad and be
carried over into the air stream and ducting.
• Water bypass may cause damage to internal electronic
components.
A294-B