20
Table 3 Main Board Connectors and Jumpers
Connector/
Jumper
Description
P2
To Power Supply
P3
To Power Supply
P4
Ribbon Cable connects to P4 of front display
P5
To PC Configurator
P7
Factory Use Only
P8
To PR-300
P9
To Printer
P10
To ALC-480 Loop Adder
P11
Factory Use Only
P13
USB Port to PC Configurator
P14
Future Use
JW1
Must be ON (default) - Allows Configuration Connection
JW2
Must be ON (default) - Annunciator End of Line
JW5
Normally open (default). Place jumper here and power down (AC and batteries) and
power back to restore Master Password. After reset, remove jumper and leave
normally open.
JW6
Normally open (default) to BLOCK remote configuration via modem. Place jumper
here to ALLOW for remote configuration. When jumper is set panel will indicate a
trouble.
JW7
On the Main Fire Alarm Module, this jumper must be removed if a PR-300 Polarity
Reversal and City Tie Module is installed. The default setting is jumper ON.
JW10
Must be in the 1-2 Position (Bottom 2 Pins) - Allows PC Connection through serial port
JW11
Place in the 1-2 Position (Bottom 2 Pins) for Serial Port or Place in the 2-3 Position
(Top 2 Pins) for Keltron Dialer.
JW12
Close pins 2 and 3 to send the debug trace to the printer. Close pins 1 and 2 to send
events to the printer. The printer is supervised when the pins are in position 2 and 3.
The default setting is the 1-2 position.
JW14
Factory set on pins 1 and 2. Do not change.
Table 4 Core Board Jumpers
Jumper
Description
JW4
Factory set closed (ON). Leave as is.
JW5
Factory set open (OFF). Leave as is.
Attention: ADVANCED INSTALLER NOTE
Setting JW5 and JW6 on the main board at start-up will revert the panel to the
default configuration.
!