41
Supervision is carried out every two minutes as follows:
1. DC voltage is supervised and if it is detected the dial tone is monitored.
2. If the phone lines are equipped with a house phone with proper connection and is in use
the supervision is suspended until the house phone is ON-HOOK again.
3. If there is an event to be reported in the dialer queue and the house phone is in use the
dialer tries the second line to report the event.
4. if that line’s house phone is also in use the dialer seizes the line. The dialer disconnects
the house phone and reports the event to the central monitoring station.
5.11
Using the Operation Menu from the Control Panel
Operations of the MR-401 Addressable Fire Alarm Control Panel can be managed via the
Operation Menu on the LCD Shared Display. Accessing the menus is done via the Numeric
Keypad and Cursor Buttons. For a complete description of how to use the Numeric Keypad
and Cursor Buttons see Numeric Keypad and Cursor Buttons on page 56.
The following items can be accessed through the Operation Menu:
•
Setting the Time on the system
•
Setting the Password on the system
•
Viewing Reports
•
Clearing Logs
•
Walk Test Function
•
Bypass Operation
•
Disconnecting Auxiliary Relays
•
Testing the Dialer
•
After Hours Operation
•
Clearing Verification Counts
•
Ground Fault Testing - Factory Use Only
Complete configuration of the system is done via the software configurator.
Summary of Contents for MR-401
Page 2: ......