48
Use the
UP
and
DOWN
cursor keys to scroll to the desired option press the
Enter
button.
The following message will show the walk test initializing.
While the walk-test is active the following message is displayed on the screen:
where nnn and mmm are continuously updated counts of the number of alarms and troubles
which have been recorded during the test (alarms includes all input circuit types tested).
Selective Output Testing
Walk Test can be operated with only a selection (up to 64) of outputs. To do this, select audible
test. The next screen will be:
Select “No” by using the right arrow key and the next screen will say:
Use the left and right arrow key to move through the outputs you wish to active during walk
test.
5.11.6
Bypass
The bypass operation has the following options:
Note:
Each event during the Walk Test is also recorded in the log. Therefore, any event
past the 200 count will clear the log and be entered as event 1 and so on.
Select Test Type
1. Audible Test
2. Silent Test
Initializing
Walk test ...
- Walktest Active -
Alarms: nnn
Troubles: mmm
Press ENTER to end
i