80
Panel Configuration/Features/Waterflow Retard
Waterflow retard
[ ] Enabled
If disabled, all the initiating circuits configured as waterflow act as non-verified alarms. If
enabled, retard operation is performed for initiating circuits configured as waterflow.
Panel Configuration/Features/Auxiliary disconnect, disconnects alarm and supervisory relay
Aux Dis Alm&Sv
[ ] Enabled
If enabled the auxiliary disconnect operation, disconnects alarm and supervisory relays disabled the
auxiliary disconnect operation has no affect on the alarm and supervisory relays. Default is disabled.
Panel Configuration/Features/Signal silence inhibit timer
Sig.sil. inh.
[x] Disabled
[ ] 10 sec
[ ] 20 sec
[ ] 30 sec
[ ] 1 min
Select the timer value for the signal silence inhibit timer.
Panel Configuration/Features/Auto signal silence timer
Auto sil. tmr
[x] Disabled
[ ] 5 min
[ ] 10 min
[ ] 15 min
[ ] 20 min
[ ] 30 min
Select timer value for the auto signal silence timer.
Panel Configuration/Features/Alarm transmit silence
Alm. xmit. sil.
[ ] Enabled
This feature allows the alarm transmits and auxiliary alarm relay to reset on “SIGNAL SILENCE” rather than
the “RESET” switch if enabled. Default is disabled.
Panel Configuration/Features/Power fail timer
Pwr fail tmr.
[x] None
[ ] 1 Hr
[ ] 2 Hrs
[ ] 3 Hrs
This feature allows a programmed delay before the AC fail trouble is transmitted by
the optional PR-300
.
(Note: the delay for transmission by the dialer is configured under Dialer Configuration – Item 4 –Time
Parameters - AC Loss Delay)