46
The maintenance report is shown in the following format.
Press the
Up
and
Down
cursor keys to scroll through all the devices on the loop for which the
maintenance report is available. If there are no dirty devices on the loop the following
message will be displayed
6. M/P Report
The MGC Protocol (MP) Report will display or list on a printer all local parameters of an MP
device currently connected on the SLC. This feature will list the internal register values of
current MP devices. Since parameter values and addresses are not disclosed to the user, this
tool is used to report information to Secutron technical support.
If the panel is connected to a printer the user will be prompted to select an output source:
If “Printer” is selected the user will be prompted to select the address range. “All” selects all
addresses from all configured loops and “Loop” selects addresses from one loop.
If “Loop” is selected the user will be prompted to enter a loop number:
If the panel does not have a printer connected or if the user selects “Screen” under the report
to menu only one address will be displayed. The user will be prompted to enter this address:
Once the report is on display it will list all the parameters of all the addresses related to the
device. In this display “Crt.” indicates report line number, “Add” indicates device current
address, “Parm#” indicates the parameter number from the current address, and “Val#”
indicates the parameter value.
Loop Number
Loop :__
Maint Report
Percent dirty :012%
No dirty devices
found
- Report To -
1. Printer
2. Screen
1. All
2. Loop
Loop Number
Loop: _
Device Address
Loop: _ Devaddr:___
Summary of Contents for MR-401
Page 2: ......