42
How to Enter the Operation Menu
1. Press the
Menu
button.
2. Use the
DOWN
Cursor key to scroll to
3. Operation
and press the
Enter
button to enter
the Operation Menu.
Figure 10 Operation Menu
3. To select an Operation use the
DOWN
Cursor key to scroll to desired choice and press
the
Enter
button.
5.11.1
Setting the Time
Sets the current date and time for the panel. Use the ‘#’ key to move the cursor forward and
the UP and DOWN key to change the date/time parameters.
5.11.2
Setting the Password
By default, no password is required to press the control buttons and enter the operation menu.
Sets the password for all three access levels. The minimum number of digits for a password is
4. For changing a specific level of password the password required is the equivalent level or
higher level.
The user is prompted to enter the access level for which the password needs to be changed.
Note:
Option 8. Test Dialer will only appear if there is a UDACT on-board.
- O p e r a t i o n M e n u -
1 . S e t T i m e
2 . S e t P a s s w o r d
3 . R e p o r t s
4 . C l e a r l o g s
5 . W a l k t e s t
6 . B y p a s s
7 . A u x . d i s c .
8 . T e s t U D A C T
9 . A f t e r h o u r s
1 0 . C l e a r v e r . c n t s
1 1 . G n d . F a u l t t e s t
1 2 . P o s i t i v e A l a r m
1 3 . E x i t
i
Date : Oct 08, 2005
Time : 10:00 PM
Access Level :1
Summary of Contents for MR-401