Doc. No.: A05280692 Rev. AE ECO: 13200 Date: 11/04/2019
63
Recommended Weekly Testing
Patient Escort and Anti-Tailgate Feature Test
1.
Enter the monitoring zone with a transmitter. The red
LED will turn ON and the door will quietly lock.
2.
Enter the primary reset code into the keypad. The red LED will turn green, the door will unlock, and you will be
able to open the door without the alarm sounding.
3.
Continue holding the door open
4.
Now close the door. The red LED will turn ON and the door will immediately relock. This is the anti-tailgate
feature.
Delayed Egress Feature Test
1.
With the door locked, apply pressure on the opening hardware of the door. The ID Exit Panel will begin to alarm
and the red LED will remain ON. The audible alarm sound will be short beeps.
2.
After 15 seconds, the audible alarm will become a continuous tone, the red LED will be ON, and the door will
release.
3.
Open the door. The LED will begin flashing red/green/red/green and the audible alarm sound will change to the
seagull sound.
4.
Close the door and enter the primary reset code. The ID Exit Panel will stop alarming, the door will relock, and
the red LED will be ON. (The transmitter is still in the monitoring zone).
Remote Keypad Test
1.
If a remote keypad has been installed with the ID Exit Panel, repeat the steps above using the Remote Keypad
to enter the primary reset code.
Push Button Test
If a remote Push Button has been installed with the ID Exit Panel, repeat the steps above using the Remote
Push Button.
Depress the Remote Push Button. The LED will turn green and you will be able to open the door without
creating an alarm condition.
Advanced Security Mode Test
1.
Make sure the Advanced Security Mode is enabled.
2.
Bring a transmitter into the monitoring zone. The red LED will turn on; the yellow LED will blink.
3.
Enter the primary reset code. The red alarm LED will flash momentarily and one beep will be heard, indicating
a valid code was entered while a monitored resident was nearby.
4.
Next, try to gain access via the Push Button ( if one is installed on your system). With a transmitter in range,
the result should be the same as above (step 3). Only by entering the secondary reset code (*567 or equivalent)
will access be granted in this situation.
Recommended Monthly Testing
Fire Alarm Release Feature Test
1.
Place the fire alarm system into the alarm mode and verify that all locks release. The KinderGUARD ID Exit
Panels will be in the fire alarm release condition. All other features of the Exit Panels will be functional.
Recommended Annual Service
Battery Replacement
The battery should be replaced annually with a rechargeable 9VDC NI-MH battery (Secure Care Part # B15360501).
SECTION 11
TESTING KinderGUARD
®
ID SYSTEM WITH LOCK
Summary of Contents for KinderGUARD ID
Page 8: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 8...
Page 9: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 9...
Page 10: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 10...
Page 75: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 75...
Page 77: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 77...
Page 78: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 78...
Page 81: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 81...