Breathing Air Cylinder Inspection
75
SCOTT SAFETY
087-0067 REV A
Breathing Air Cylinder
Inspection
This section covers inspection of the breathing air cylinder.
“Warnings and Cautions – Working with Compressed Air” on page xix.
Refer to current applicable publications on compressed gas cylinder inspection
available from Compressed Gas Association Inc., 1725 Jefferson Davis Hwy., Suite
1004, Arlington, VA 22202, (703-412-0900) for a detailed explanation of cylinder
inspection procedures.
1
Check the latest cylinder hydrostatic test date to ensure it is current. All breathing
air cylinders must be visually inspected regularly and hydrostatically tested by a
licensed cylinder retester in accordance with the appropriate US Department of
Transportation (DOT) specification or applicable DOT exemption, or in
accordance with the appropriate Transport Canada (TC) Permit of Equivalent
Level of Safety. The date of manufacture marked on the cylinder is also the date of
the first hydrostatic test. For other breathing air cylinders, consult the cylinder
manufacturer’s recommendations and the requirements of the appropriate national
regulatory agencies. It is the responsibility of your organized respiratory protection
program to arrange for visual inspection and hydrostatic testing of cylinders by a
licensed retester. See
.
Figure 40
Breathing Air Cylinder Markings
2
Visually inspect cylinder and valve assembly for physical damage such as dents or
gouges in metal or in composite wrapping. Cylinders which show physical damage
or exposure to high heat or flame, such as paint turned brown or black, decals
Table 26
Cylinder Manufacture Date & Identification and Pressure Rating
REFERENCE
NUMBER
ITEM
1
Serial Number - A serial number followed by the name of the original
manufacturer, Luxfer, is located below or immediately following the DOT
marking above.
2
Manufacturing Date - The independent inspection agency 9IIA) official
mark, which must be placed near the serial number. The marking must
contain date (Month and Year) of the manufacturing date and initial
hydrostatic test for that cylinder. (Month A Year)
3
REE - The REE is the Rejectable Elastic Expansion for this cylinder. The
hydro test result needs to be less than this number for the cylinder to
continue to be in use. The REE marking is in cubic centimeters.
4
Permit Number - Each cylinder is marked with a DOT permit number. The
DOT Special Permit (SP) number or DOT Exception (E) number followed
by service pressure expressed in pounds per square inch gauge (psig) and if
applicable, Transport Canada Permit number followed by service pressure
expressed in bar.
TC-SU 5134-310
DOT-E 10915-4500
OK 12345 LUXFER
5 A 07 REE: 75
1
2
4
3
Summary of Contents for HushAir Connect 7500
Page 1: ...User Guide 087 0067 Rev A HushAir Connect 7500 COMPRESSOR SYSTEM ...
Page 2: ......
Page 3: ...HushAir Connect 7500 User Guide COMPRESSOR SYSTEM 087 0067 Rev A ...
Page 8: ...IV CONTENTS 087 0067 REV A SCOTT SAFETY ...
Page 12: ...X LIST OF TABLES 087 0067 REV A SCOTT SAFETY ...
Page 42: ...20 CHAPTER 2 INSTALLATION 087 0067 REV A SCOTT SAFETY ...
Page 73: ...Configuring the System 51 SCOTT SAFETY 087 0067 REV A Figure 27 Override Status Screen ...
Page 106: ...84 CHAPTER 5 MAINTENANCE 087 0067 REV A SCOTT SAFETY Figure 48 Oil Drain Location 3 1 2 ...
Page 112: ...90 APPENDIX A SPECIFICATIONS 087 0067 REV A SCOTT SAFETY ...
Page 119: ......