Date Code 970103
Communications
3-23
SEL-251, -2, -3 Instruction Manual
A list of relay settings follow. Setting ranges and explanations have been added.
=>>
SET 1 <ENTER>
SET clears events. CTRL-X cancels.
SEL-151-R407 Group Settings
Group = 1
Active group = 1
Enter data, or
<ENTER>
for no change
Range
ID
: Example 21.6 kV distribution feeder
?
39 characters
CTR
: ................................................................... = 120.00
?
0.001-10000
Current transformer ratio
PTR
: ................................................................... = 180.00
?
"
Potential transformer ratio
R1
: Ohms Pri .................................................... = 0.58
?
0.001-10000
Positive-sequence line resistance
X1
: .................................................................... = 1.50
?
"
Positive-sequence line reactance
R0
: .................................................................... = 1.44
?
"
Zero-sequence line resistance
X0
: .................................................................... = 4.56
?
"
Zero-sequence line reactance
RS
: .................................................................... = 0.00
?
"
Current-limiting reactor resistance
XS
: .................................................................... = 0.00
?
"
Current-limiting reactor reactance
LL
: Line Len..................................................... = 2.42
?
0.001-10000
Line length (unitless); If LL=0.001, no fault location information
DATC
: Dem, 5-60 min ........................................... = 15
?
Demand ammeter time constant
PDEM
: Ph Dem Thr, A sec .................................... = 12.00
?
1.00-12.00
Phase demand ammeter threshold for
PDEM
QDEM : 3I2 Dem Thr, A sec ................................... = 12.00
?
0.25-12.00
Negative-sequence demand ammeter threshold for
QDEM
NDEM : IR Dem Thr, A sec..................................... = 1.00
?
"
Ground/residual demand ammeter threshold for
NDEM