5-6
Applications
Date Code 20000421
SEL-251, -2, -3 Instruction Manual
Using SEL
OGIC
Control Equations:
S(123)N =
50C
Figure 5.5: 50C Delayed by TSPU Time
If
50L
is supervised by
ST
,
50L
continues to be disabled for time period TSPU after the circuit
breaker closes and load is picked up. Set TSPU slightly greater than the potential cold load
inrush time.
Continuing with SEL
OGIC
Control Equations:
B
(12)
=
50L
E
(34)
=
ST
(time delayed
50C
)
V
(56)
=
B
*
E
TR(1246) =
V
+...
(TR is the programmable trip condition)
effectively, TR(1246) =
50L
*
ST
+...
close TRIP output contacts = TR + ...
If the TSDO setting exceeds the longest reclosing relay open interval time setting (79OI1, 79OI2,
etc.),
ST
will not drop out during the reclose cycle. Thus,
50L
remains enabled throughout the
cycle.
ST
drops out when TSDO expires after the recloser goes to lockout (the circuit breaker is
open and
50C
= 0). This may be desirable since typical open interval times are not long enough
to warrant concern about cold load inrush. Thus,
50L
is disabled for TSPU time only after the
circuit breaker closes from the lockout state.
To disable
50L
only after the circuit breaker closes from the lockout state, make the following
settings.
Using SEL
OGIC
Control Equations:
S
(123)
=
50C
B
(12)
=
50L
E
(34)
=
79RS
+
79CY
+
ST
V
(56)
=
B
*
E
TR(1246) =
V
+...
(TR is the programmable trip condition)