Date Code 20000421
Specifications
2-17
SEL-251, -2, -3 Instruction Manual
SEL
OGIC
Control Equations Settings in Each Setting Group
When you switch groups, you switch logic settings as well as relay element settings. You can
program groups for different operating conditions, such as feeder paralleling, station mainte-
nance, seasonal operations, and cogeneration on/off.
T
ARGETS
Read targeting information locally by inspecting the LEDs or remotely with the TARGET com-
mand and event reports. The TARGET command can access other information as well (see
Section 3: Communications
).
The INST target indicates that no overcurrent condition in Relay Word row R1 has been asserted
longer than the ITT (instantaneous target time) timer setting before TRIP asserts. This gives you
control over what qualifies as a close-in fault. Setting ITT=0 defeats the INST target.
The phase current indicators (A, B, C) show which phases exceed the 51P pickup setting at the
time of trip.
The negative-sequence and residual current indicators (Q, N) similarly show if these currents
exceed the respective 51QP and 51NP pickup settings at the time of trip.
The last two indicators (RS, LO) show the state of the reclosing relay (reset or lockout).
Figure 2.9:
SEL-251 Relay Front Panel Target LEDs
The FAULT TYPE LEDs latch and remain lit until the TRIP output deasserts and one of the
following occurs:
•
Next trip occurs
•
Operator presses front panel TARGET RESET button
•
Operator executes TARGET R command
When a new TRIP occurs, the FAULT TYPE LEDs clear, then display and latch the FAULT
TYPE targets for the new TRIP condition.
When an operator presses the TARGET RESET button, all eight LEDs illuminate for a one-
second lamp test and to indicate that the relay is operational.
M
ULTIPLE
S
HOT
R
ECLOSING
R
ELAY
The four-shot reclosing relay has individual open interval times for each shot and a settable reset
interval timer.