Date Code 20000421
Applications
5-9
SEL-251, -2, -3 Instruction Manual
Some applications may require that the permissive trip input supervise a low-set ground residual
instantaneous overcurrent element. In the following example, 79SH also supervises the low-set
ground/residual instantaneous overcurrent element
50NL
in a fuse-saving scheme.
Using SEL
OGIC
Control Equations:
A
(12)
=
51NT
(ground/residual time-overcurrent element)
B
(12)
=
50NL
(low-set ground residual instantaneous overcurrent element)
E
(34)
=
79SH
F
(34)
=
IN5
(input
IN5
will function as a permissive trip input)
V
(56)
=
A
*
F
W
(56)
=
B
*
E
*
F
TR(1246)
=
V
+
W
+...
(TR is the programmable trip condition)
effectively, TR(1246)
= (
51NT
*
IN5
)+(
50NL
*
79SH
*
IN5
)+...
which reduces to: TR(1246)
= [
51NT
+(
50NL
*
79SH
)]*
IN5
+...
close TRIP output contacts =
TR
+ ...
Disable Ground/Residual Overcurrent Elements with Block Trip Input
When a block trip input is energized, selected overcurrent elements are disabled for tripping.
When a block trip input is de-energized, selected overcurrent elements are enabled for tripping.
This function is the opposite of a permissive trip input.
Inputs IN5 and IN6 are available in the Relay Word and can be effectively used as block trip
inputs.
Using SEL
OGIC
Control Equations:
A
(12)
=
51NT
(ground/residual time-overcurrent element)
L(1234)
=
IN5
(input IN5 to function as a block trip input)
V
(56)
=
A
*
!L
(
!L
=NOT(L) = NOT(
IN5
))
TR(1246)
=
V
+...
(TR is the programmable trip condition)
effectively, TR(1246) =
51NT
*NOT(
IN5
)+...
close TRIP output contacts = TR + ...
Some applications may require that the block trip input supervise a low-set ground residual
instantaneous overcurrent element. In the following example,
52AT
also supervises the low-set
ground/residual instantaneous overcurrent element
50NL
in a fuse-saving scheme.
Using SEL
OGIC
Control Equations:
A
(12)
=
51NT
(ground/residual time-overcurrent element)
B
(12)
=
50NL
(low-set ground residual instantaneous overcurrent element)
E
(34)
=
52AT
L(1234)
=
IN5
(input IN5 will function as a block trip input)
V
(56)
=
A
*
!L
(
!L
=NOT(L) = NOT(
IN5
))
W
(56)
=
B
*
E
*
!L
TR(1246) =
V
+
W
+...
(TR is the programmable trip condition)