7-6
Maintenance and Testing
Date Code 20000421
SEL-251, -2, -3 Instruction Manual
♦
♦
Step 5
Purpose:
Apply control voltage to the relay and start Access Level 0 communications.
Method:
Turn on the relay power. All front panel targets should illuminate when you press
the TARGET RESET button. If not, be sure that power is present and check the fuse
or fuses. The following message should appear on the terminal:
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 01:01:01
SEL-151
=
The ALARM relay should pull in, holding its "b" contacts (terminals 15,16) open. If
the relay pulls in but no message is received, check the terminal configuration. If
neither occurs, turn off the power and refer to
Troubleshooting
later in this section.
The = prompt indicates that communications with the relay are at Access Level 0,
the first of three levels. The only command accepted at this level is ACCESS, which
opens communications on Access Level 1.
Note:
If you are using a battery simulator, be sure the simulator voltage level is
stabilized before turning the relay on.
♦
♦
Step 6
Purpose:
Establish Access Level 1 communications.
Method:
Type
ACCESS
and press
<ENTER>
. At the prompt, enter the Access Level 1
password OTTER and press
<ENTER>
. The => prompt should appear, indicating
that you have established communications at Access Level 1.
♦
♦
Step 7
Purpose:
Verify relay self-test status.
Method:
Type
STATUS
and press
<ENTER>
. The following display should appear on the
terminal:
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 01:04:56
SELF-TESTS
W=Warn F=Fail
IR IA IB IC VA VB VC
OS 0 0 0 0 0 0 0
PS 5.08 14.92 -14.99
RAM ROM A/D MOF SET
OK OK OK OK OK
=>