Date Code 970103
Communications
3-5
SEL-251, -2, -3 Instruction Manual
You may enter Access Level 1 with the ACCESS command and first password. The Level 1
password is factory-set to OTTER and may be changed with the PASSWORD command in
Access Level 2. Most commands may be used in Access Level 1.
Critical commands such as SET operate only in Access Level 2. You may enter Access Level 2
with the 2ACCESS command and second password. The Level 2 password is factory-set to
TAIL and may be changed with the PASSWORD command.
Startup
Immediately after power is applied, the relay transmits the following message to the port(s)
designated automatic:
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 01:01:01
SEL-151
=
The ALARM relay should pull in.
The = represents the Access Level 0 prompt.
The relays are shipped with Port 2 designated automatic; you may use the SET command to
change this designation (see SET command, AUTO setting). This allows you to select Port 1,
Port 2, or both ports to transmit automatic responses from the relay.
To enter Level 1, type the following on a terminal connected to Port 2:
=ACCESS <ENTER>
ACCESS <ENTER>
The response is:
Password: ? @@@@@@
Enter the Level 1 password
OTTER
and press
<ENTER>
. The response is:
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 01:01:44
Level 1
=>
The Access Level 1 prompt is =>. Now you can execute any Level 1 command.
Use a similar procedure to enter Access Level 2:
Type
2ACCESS <ENTER>
. The relay pulses the ALARM relay contact closed for
approximately one second in response to your access attempt. Enter the password
TAIL
when
prompted. After you enter the second password, the relay opens access to Level 2, as indicated
by the following message and Level 2 prompt (=>>):