![Schweitzer Engineering Laboratories SEL-251 Instruction Manual Download Page 28](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-251/sel-251_instruction-manual_1216702028.webp)
2-14
Specifications
Date Code 20000421
SEL-251, -2, -3 Instruction Manual
Table 2.2: SEL-251 Relay Word
R1
51P
50L
50H
51QP
50Q
51NP
50NL
50NH
R2
51T
50LT
50C
51QT
50QT
51NT
50NLT
27
R3
79RS
79CY
79LO
79SH
52AT
52BT
IN6
IN5
R4
PDEM
QDEM
NDEM
TF
CF
TCMA
ST
TRIP
R5
A
B
C
D
E
F
G
H
R6
J
KT
!L
V
W
X
Y
ZT
! indicates NOT
51P
Phase time-overcurrent element pickup
50L
Phase definite-time overcurrent element pickup
50H
Phase instantaneous overcurrent element
51QP
Negative-sequence time-overcurrent element pickup
50Q
Negative-sequence definite-time overcurrent element pickup
51NP
Ground/Residual time-overcurrent element pickup
50NL
Ground/Residual definite-time overcurrent element pickup
50NH
Ground/Residual instantaneous overcurrent element
51T
Phase time-overcurrent element
50LT
Phase definite-time overcurrent element
50C
Phase instantaneous overcurrent element (can override voltage control by
27
)
51QT
Negative-sequence time-overcurrent element
50QT
Negative-sequence definite-time overcurrent element
51NT
Ground/Residual time-overcurrent element
50NLT
Ground/Residual definite-time overcurrent element
27
Phase undervoltage element for internal torque control and blown-fuse detection
79RS
Reclosing relay is in the reset state
79CY
Reclosing relay is in the reclose cycle state
79LO
Reclosing relay is in the lockout state
79SH
Shot bit; asserts for shots selected by the M79SH setting
52AT
Time delayed 52A
52BT
Inverse of
52AT
IN6
Input IN6 bit; asserts for control voltage applied to input IN6
IN5
Input IN5 bit; asserts for control voltage applied to input IN5