General operations | Query alarm counter
B-HB-0133EN
Operating panel Integral MAP | User manual
25
5.6.3
Operation of a range of single elements (detector of a
detector zone)
1.
Select the element type
Zone
by pressing the button
N
.
2.
Enter number of the detector zone using the numerical buttons of the keypad
X
.
3.
Press the slash key (
/
) to enter the single element hyphen (
/
).
4.
Enter the the first (lowest) number of the detector in the detector zone using the nu-
merical buttons of the keypad
X
.
5.
Press the slash key (
/
) to enter the range hyphen (
-
). The display switches to range
operation.
6.
Enter the the last (highest) number of the detector in the detector zone using the nu-
merical buttons of the keypad
X
.
u
Example for detectors 3 – 20 of a detector zone 1:
RANGE OPERATION
ZONE
1/3-20
0000
0000
0000
0000
0001
7.
Confirm with the enter button
D
.
8.
The selected detectors of the detectors zone can be operated together with the de-
sired command (
d
–
g
).
5.7
Query alarm counter
| Query alarm counter
Pressing the button
Menu
a
opens the menu for additional options. Using the scroll
buttons
E
/
F
to select the entry
ALARMCOUNTER
. Pressing the Enter key
D
shows the
number of alarms that have occurred so far.