System operation in the event of an alarm | Reset (mute) or disable sirens
18
Operating panel Integral MAP | User manual
B-HB-0133EN
4.5
Reset (mute) or disable sirens
| Reset (mute) or disable sirens
Only use this function when the building has been completely cleared.
Pressing the button
Silence/ Resound
r
resets activated sirens (mutes them), but
these are reactivated together with the arrival of the next alarm. LED lights up, if the
sirens were reset. Pressing the button again switches the sirens on again. Reset the
sirens is possible with authorisation level 1.
Pressing the button
Disable/Enable
s
switches off the main siren and all other sirens
and alarm areas. The LED next to the button and the
l
LED lights up, if the alarm sys-
tems are disabled. The sirens are not activated, even not in case of an occurring alarm.
Pressing the button again switches the sirens on again. Disabling the sirens is possible
with authorisation level 2.
4.6
Reset alarm
| Reset alarm
(An authorisation code must be entered for this to be permitted)
Only use this function if it is ensured that there is no longer any danger or if you are in-
structed to do so by the fire brigade. The cause of the alarm message must be elimin-
ated. If the cause of the alarm is not resolved (for example there is still smoke, manual
call point was not reset) the alarm will once again be displayed after 30 seconds.
If it has been proven within the intervention period that there is no fire, then the alarm
can be reset by pressing the
Reset Alarm/System
E
button without the fire brigade be-
ing notified.
If the transmission equipment is actuated (LED
Actuated
F
flashes), the alarm can no
longer be reset.
4.7
Transmission system actuated
| Transmission system actuated
If the LED
Actuated
F
flashes, then the location offering assistance has already been in-
formed of the alarm.
Do not press another button, wait for the support and assistance staff to arrive. Have the
necessary plans ready.
NOTE
The intervention function is only permissible for detector zones with smoke
detectors. Alarm messages generated by the heat and flame detector as
well as the manual call point trigger the transmission system without delay
and are immediately forwarded to the emergency services.